9.12.4
Setting for Rampup time and Rampdown time
By separate menus for Rampup time and Rampdown time an adjustment is possible to individual
system conditions.
This function is switched behind the actual controller function.
Rampup time
Rampup time
Time setting in which the automatic controller output from 0 % to 100 % rises.
Setting range: 0...250 sec.
Factory setting: 10 / 20 / 30 / 40 sec. (depending on device type)
Rampdown time
Rampdown time
Time setting in which the automatic controller output from 100 % to 0 % reduces.
Setting range: 0...250 sec.
Factory setting: 10 / 20 / 30 / 40 sec. (depending on device type)
0 .. 100 %
3
4
1
2
09.05.2007
v_hochlaufzeit_ruecklaufzeit.vsd
1
external Signal
2
Setting
3
Rampup time
4
Rampdown time
9.12.5
Setting Rolling direct.
Attention!
It is essential to check the direction of rotation of the fan during the initial commissioning. To do this,
note the direction of the arrow on the fan housing. We will not be responsible under any circumstances
for warrantee for damage caused because the direction of rotation is wrong!
When connected in accordance with the connection diagram, the standard rotary direction
“
RIGHT
”
=
|
CW
|
results under factory settings. A change of direction is feasible by exchanging the phase
sequence in the motor connection or through reprogramming.
Rotat. Direction
By selection of the parameter
“
Direction of rotation
”
and
following pressing the
P
key, the direction of rotation can
changed to
|
CCW
|
for anti-
“
clockwise
”
=
|
CCW
|
direction of
rotation.
Pressing the
P
key causes the value that has been set to be
accepted.
Rotat. Direction
If the rotary direction is reversed with an available modulation, it is initially reduced to
“
0
”
(discon-
nected) and subsequently increased back to the default value.
Operating Instructions
Fcontrol
–
model series FXDM
Programming
L-BAL-E072-GB 1642 Index 008
Part.-No.
77/105