Sheet metal housing
IP54
1
Inlet mains connection (40 mm)
2
Inlet motor connection (40 mm)
3
Inlet control cables (20 mm)
IP20
1
Inlet mains connection (32 mm)
2
Inlet motor connection (32 mm)
3
Ridges for connecting the control cables
4
Cut-out for control cables in the cover
Information
•
Cable glands can be used alternatively (not included in delivery). The manufacturer
’
s speci
fi
cations
for tightening torque and sealing area must be observed!
•
Openings which are not needed must be sealed!
4.5
Outdoor installation
Outdoor installation is possible up to -20
°
C when the controller supply is not switched off. Installation
must be protected from the effects of weather as much as possible, including protection from direct
sunlight!
4.6
Installation location for agriculture
When using for animal keeping, do not install the device directly in the stable but in a separate room
with a lower pollutant load. This helps to avoid damages caused by pollutant gases (e.g. ammonia
fumes, hydrogen sulphide fumes).
4.7
Temperature in
fl
uences during commissioning
Avoid condensation in the controller and functional faults attributable to condensation by storing the
controller at room temperature!
5
Electrical installation
5.1
Safety precautions
Danger due to electric current
•
Work on electric components may only be carried out by trained electricians or by persons
instructed in electricity under the supervision of an electrician in accordance with electrical
engineering regulations.
•
The 5 electrical safety rules must be observed!
•
It is forbidden to carry out work on electrically live parts. Even after disconnection, the dc-link is still
live. Always wait at least 3 minutes.
•
Cover neighbouring electrical equipment during installation work.
•
Other measures may be necessary to achieve safe electrical isolation.
•
A second person must always be present when working on energized parts or lines who
disconnects in case of emergency.
•
Inspect electrical equipment periodically: retighten loose connections
–
immediately replace
damaged lines and cables.
•
Always keep switch cabinets and all electrical supply facilities locked. Access is only allowed for
Operating Instructions
Fcontrol
–
model series FXDM
Electrical installation
L-BAL-E072-GB 1642 Index 008
Part.-No.
14/105