Additional menu item for mode
5.02
with outside-temperature dependent target-setpoint
Outside-temperature dependent target-setpoint
Außentemperatur
P-min SA
[m
3
/h]
-15 °C
min. Temperatur
30 °C
T-Start
Sollwert 1
[m
3
/h]
Sollwert 2
[m
3
/h]
07.02.2007
v_sollwert_aussentemp_abhaengig_m3h.vsd
S1
Setpoint1
S2
Setpoint 2
P-Min SA
Minimum air volume
T-min
Minimum temperature
T-Start
Setpoint reducing will start below this outside temperature
AT
Outdoor temperature
An outside temperature compensation can be
activated (sensor connection
“
E2
”
to
“
Analog In
2
”
) when being operated as a air volume regu-
lation device.
An optimal building climate, e.g., can be
achieved through this. Through this function,
the set and active Setpoint 1/2 is automatically
changed proportional to the measured outside
temperature (
Info:
“
Setpoint control
”
).
T-Band SA
T-Band SA
Temperature range in which the setpoint change continiously with outside temperature
T-Start SA
T-Start SA
Setpoint reducing will start below this outside temperature
P-Min SA
P-Min SA
Minimum pressure for very low outside temperature
9.6
Air velocity control
6.01
9.6.1
Base setup
6.01
Base setup
Base setup
Mode
Mode
Mode selection
6.01
E1 Analog In
E1 Analog In
For mode
6.01
“
E1 Analog In
”
factory setting to
“
MAL1
”
Selection sensor measuring range: MAL1, MAL10
Alternative selection signal: 0 - 10 V, 0 - 20 mA, 4 - 20 mA (
jumper for input signal).
The sensor measurement range must be entered in order to display the actual value
correctly. Example with a 0 - 10 V sensor and 0 - 5 m/s measurement range (propor-
tional output signal).
E1 Analog In = 0 - 10 V, E1 Min. = 0.0 m/s, E1 Max. = 5.0 m/s, E1 Decimals = 1, E1
Unit = m/s
E1 Offset
Sensor calibration with calibrated comparison device
Operating Instructions
Fcontrol
–
model series FXDM
Programming
L-BAL-E072-GB 1642 Index 008
Part.-No.
49/105