authorized persons using a key or special tool.
•
Operating the device with the housing cover removed is prohibited because energized, exposed
parts are present inside the device. Disregarding this regulation can lead to severe personal injury.
•
The required protective earth connection is established using screws between the housing parts in
metal terminal space covers and housing casings. Commissioning is only permissible after these
screws have been properly attached!
•
The device owner is responsible for the EMC of the entire plant according to the locally applicable
standards.
•
Metal screwed-connections are not permitted in plastic housing parts because there is no potential
equalization.
•
Never clean electrical equipment with water or similar liquids.
Information
The respective connections are represented in the enclosure of this manual (
Connection diagram)!
5.2
Terminal compartment
Example: Position of terminals for devices in sheet metal housing
1
Line
2
Motor
3
Modulation
4
Indication relays
5
MODBUS
Maximum cross sections of terminals for power section
Type
Line
Motor
rigid
fl
exible
rigid
fl
exible
FXDM2.5(A)M
2,5 mm
2
2,5 mm
2
2,5 mm
2
2,5 mm
2
FXDM5(A)M
2,5 mm
2
2,5 mm
2
2,5 mm
2
2,5 mm
2
FXDM8(A)M
2,5 mm
2
2,5 mm
2
2,5 mm
2
2,5 mm
2
FXDM10(A)M
2,5 mm
2
2,5 mm
2
2,5 mm
2
2,5 mm
2
FXDM14(A)M
4 mm
2
4 mm
2
4 mm
2
4 mm
2
FXDM18(A)M
4 mm
2
4 mm
2
4 mm
2
4 mm
2
FXDM22(A)M
6 mm
2
6 mm
2
6 mm
2
6 mm
2
FXDM32(A)M(E)
16 mm
2
10 mm
2
10 mm
2
6 mm
2
FXDM40(A)M(E)
25 mm
2
16 mm
2
16 mm
2
10 mm
2
FXDM50(A)M(E)
25 mm
2
16 mm
2
16 mm
2
10 mm
2
Operating Instructions
Fcontrol
–
model series FXDM
Electrical installation
L-BAL-E072-GB 1642 Index 008
Part.-No.
15/105