28
or setting temperature.
9.7.9 Turbo function in heating mode. (press the “TURBO” button on remote controller)
1)
Elevate current frequency (excluding F8) to a higher grade. If indoor fan is in low speed or pause
caused by defrosting or anti-cold-wind function, frequency of compressor will not be elevated one grade until
these limit has been released.
2)
Indoor fan changes to turbo speed and anti-cold-wind function is valid.
9.8 Auto mode function
9.8.1 This mode can be chosen with remote controller and the setting temperature can be changed between 17~30 .
In auto mode, the machine will choose cooling, heating or fan-only mode according to
Δ
T(
Δ
T =T1-Ts).
Δ
T=T1-Ts Running
mode
Δ
T 1 Cooling
-1
≤Δ
T
≤
1 Fan-only
Δ
T -1 Heating
9.8.2 Indoor fan will choose auto speed of relevant mode.
9.8.3 If the machine switches mode between heating and cooling, compressor will keep stopping for 15 minutes and then
rechoose mode according to
Δ
T.
9.8.4 If the setting temperature is modified, the machine will rechoose running function.
9.9 Forced operation function
9.9.1 Forced cooling and auto function can carry out with a touch button. In these two modes, the machine can be
changed by remote controller to any other mode at any moment.
9.9.2 When the machine is off, pressing the touch button once, the unit will enter forced auto mode. When the machine is
off, pressing the touch button twice within 5s, the unit will enter forced cooling mode. When the unit is running at
forced auto or forced cooling mode, pressing the touch button continuously, the unit will be turned off.
9.9.3 In forced operation mode, all general protections is available.
9.9.4 In forced cooling mode, the unit will run with fixed frequency F2 at low speed. 30 minutes later, the unit will turn to
normal auto mode with setting temperature 24 .
9.9.5 In forced auto mode, the unit will run with setting temperature 24 .
9.10 Action of 4-way valve
In heating, fan-only, standby or turning off mode, 4-way valve is off, while in cooling\drying and forced cooling mode
4-way valve is on. If the machine changes operation mode, 4-way valve will be delayed off 2 minutes after
compressor stop. For defrosting, please refer to the passage “defrosting mode”.
9.11 Two speeds outdoor fan function
9.11.1 Outdoor fan starts at the same time with compressor, but stops 30 seconds later than compressor ‘s stop.
9.11.2 Outdoor fan action in heating mode(including heating in auto mode).
Содержание S 3025
Страница 1: ...S3025 S3032...
Страница 9: ...6 3 Dimension 3 1 Indoor Unit S3025 S3032 Model W mm H mm D mm S3025 710 250 189 S3032 790 275 190...
Страница 10: ...7 3 2 Outdoor Unit...
Страница 13: ...10 5 Refrigerant cycle diagram...
Страница 14: ...11 6 Wiring diagram 6 1 Indoor Unit S3025 S3032...
Страница 15: ...12 6 2 Outdoor Unit S3025 S3032...
Страница 40: ...37...