26
9.7.2 Indoor fan speed can be set as high, medium, low or auto grade, but anti-cold-wind function is preferential.
Auto fan action in heating mode.
9.7.3 After start the operation frequency of compressor submits to following rule:
When the machine runs, if
Δ
Th stays in a zone for 3 minutes, action of frequency is as follow:
Zone A: Elevate the current frequency one grade, and not stop until the maximum grade.
Zone B: Keep the current frequency.
Zone C: Descend the current frequency one grade.
Zone D: Compressor stops after running with F1 for 60 minutes or when
Δ
Th 6 .
9.7.4 Outdoor unit current control in heating mode.
9.7.5 Indoor heat exchanger high temperature protection.
If T2 60 , the compressor will stop and not resume until T2 48 .
9.7.6 Defrosting mode.
1)
Condition of defrosting.
Condition 1:
If T4 0 ,
Remark:
Δ
Tcon can be changed among 0, -2,- 4 , the default is 0
A
5.0
4.5
3.0
2.5
D
C
Δ
Th=(ro
om temp
) – (s
etti
ng
Te
m
p
) –
Δ
Tc
on
3.5
B
I3HEAT
I2HEAT
I1HEAT
comp. pause
freq. descends if curr. rises;
freq. remains if curr. descends
running normally
out
door unit
curr
ent
Δ
T=(roo
m
temp)
– (s
etti
ng
Te
mp)
medium
2.5
2.0
1.5
1.0
low
high
Содержание S 3025
Страница 1: ...S3025 S3032...
Страница 9: ...6 3 Dimension 3 1 Indoor Unit S3025 S3032 Model W mm H mm D mm S3025 710 250 189 S3032 790 275 190...
Страница 10: ...7 3 2 Outdoor Unit...
Страница 13: ...10 5 Refrigerant cycle diagram...
Страница 14: ...11 6 Wiring diagram 6 1 Indoor Unit S3025 S3032...
Страница 15: ...12 6 2 Outdoor Unit S3025 S3032...
Страница 40: ...37...