Installation and Operating Instructions V03
27
5.4.5 Overvoltage category
The inverter can be deployed in grids of installation category III or lower, as defined
under IEC 60664-1. This means that it can be permanently connected at the
grid-connection point in a building. In installations involving long outdoor cable routing,
additional overvoltage-reducing measures must be taken so that the overvoltage
category is reduced from IV to III.
5.4.6 Rating of miniature circuit-breaker
No load should be applied between the circuit-breaker and the inverter. Use dedicated
circuit-breakers with load switch functionality for load switching. The selection of the
circuit-breaker rating depends on the wiring design (wire cross-section area), cable
type, wiring method, ambient temperature, inverter current rating etc. Derating of the
circuit breaker rating may be necessary due to self-heating or if exposed to heat.
The maximum output currents of the inverters can be found in the following table.
Type
Zeverlution
1000S
Zeverlution
1500S
Zeverlution
2000S
Zeverlution
3000S
Max. output current
5.5A
7.5 A
10 A
15 A
Recommended fuse
type gL/gG or
comparable circuit
breaker rating
16 A
16 A
16 A
25A
Danger to life due to fire
• You must protect each inverter with an individual miniature circuit-
breaker in order that the inverter can be disconnected safely.