Installation and operating instructions
9.3 Display messages
Along with the various operating states, various messages may be shown on the
display as follows.
State
Error code
Description
Causes
Initialization
Waiting
Initial PV voltage is between Min. DC input
voltage and start-up DC input voltage of
the inverter.
Checking
The inverter is checking feeding conditions
after initial PV voltage exceeds start-up
DC input voltage of the inverter.
Reconnect
The inverter is checking feeding conditions
after the last fault has been solved.
Normal
Normal
The inverter is operating normally.
Fault
9
GFCI Fault
GFCI detection circuit is abnormal.
8
AC HCT Fault
Output current sensor is abnormal.
46
High DC Bus
The voltage of DC Bus exceeds the
permitted upper limit.
35
Utility Loss
The utility cannot be detected, which may
be caused by no utility, grid disconnected,
AC cable damage, fuse broken or island.
40
Over Temp.
The internal temperature exceeds the
permitted value.
33
Fac Fault
The grid frequency lies outside the
permitted range.
34
Vac Fault
The grid voltage lies outside the permitted
range.
37
PV Overvoltage
The voltage of the strings exceeds the
permitted upper limit.
36
Ground Fault
The residual current exceeds the
permitted upper limit.
4
DC INJ. High
Output DC feed-in exceeds the permitted
upper limit.