Installation and Operating Instructions V01
21
5.4.6 AC circuit breaker
No consumer load should be applied between AC circuit breaker and the inverter. The
selection of the AC circuit breaker rating depends on the wiring design (wire
cross-section area), cable type, wiring method, ambient temperature, inverter current
rating, etc. Derating of the AC circuit breaker rating may be necessary due to
self-heating or if exposed to heat.
The maximum output current of the inverters and recommended AC circuit breaker
can be found in the following table.
Type
Max. output current
Recommended AC circuit breaker rating
TLC4000
6.0 A
16A
TLC5000
7.5 A
TLC6000
9.1 A
TLC8000
12.1 A
20A
TLC10000
15.2 A
Danger to life due to fire
You must safeguard each inverter with an individual AC circuit breaker in order that the
inverter can be disconnected safely.