Introduction
025-9209K
11
A MODBUS SCADA system with a Model 1700 controller is shown in Figure 2.
In a MODBUS system, the PC can communicate with up to 150 Model 1708 or Model 1716
RTUs over radio or wireline through a single Model 1700 controller. A system can be
expanded beyond 150 RTUs by adding additional controllers and using additional serial ports
on the PC. The total number of RTUs in a system is limited only by the number of serial
ports available on the PC, and by the MODBUS slave address limit of 247.
Modbus PLC
- or -
PC with Modbus
SCADA Program
M1708/
M1716
M1708/
M1716
M1708/
M1716
RF
RF
RF
RS232
MODBUS Protocol
M1708/
M1716
RF - Store & Forward
Note: all RF connections could be replaced with leased lines
M1700
with
MODBUS
option
M1708/1716
with
MODBUS
option
RS232
MODBUS
Protocol
Figure 2. Generalized MODBUS System
CONNECTIONS
Main Power
Flow Detector
Door Open
High Water
High Temperature
Panic Button
Model 1716
Remote Terminal Unit
Digital #1
Inputs
•
•
•
#16
Analog #1
Inputs
•
•
•
#8
Digital Outputs
#16
•
•
•
#1
R
adi
o
C
onnec
tio
ns
Battery Level
Tank Level
Pump Control On/Off
Alarm On/Off
Panic Acknowledge On/Off
Back Up Power On/Off
Figure 3. Model 1716 RTU Standard Connections for a Pump Site
A standard application of monitoring and controlling a remote pump site could be
accomplished by using output #1 to control the pumps on/off switch and by connecting input
#1 to a flow meter to determine if the pump is pumping. If the control relay on the RTU is
damaged, the pipe is blocked, or a short or open circuit to the pump control has occurred,
then the RTU will report that no liquid is flowing.
Содержание 1708
Страница 1: ...Models 1708 and 1716 Remote Terminal Units Installation and Operation Manual 025 9209K...
Страница 8: ...Contents 025 9209K 8...
Страница 56: ...025 9209K 56...
Страница 60: ...Repair 025 9209K 60 MODEL 1700 SERIES ENCLOSURE OUTLINE 024 0057B...
Страница 61: ...Repair 025 9209K 61 MODEL 1700 SERIES ENCLOSURE INSTRUCTIONS 024 0056D Sheet 1 of 2...
Страница 62: ...Repair 025 9209K 62 024 0056D Sheet 2 of 2...
Страница 63: ...Repair 025 9209K 63 MODEL 1708 REMOTE TERMINAL UNIT SILKSCREEN 702 9439F...
Страница 64: ...Repair 025 9209K 64 MODEL 1716 REMOTE TERMINAL UNIT SILKSCREEN 702 9440F...
Страница 72: ...Appendix B 025 9209K 72...
Страница 80: ...Glossary 025 9209K 80...