025-9209K
15
OPERATION
GENERAL OPERATION
The Model 1708 and Model 1716 Remote Terminal Units (RTUs) perform two basic tasks:
1.
RTUs report changes in input/output to the Controller
2.
RTUs respond to commands from the Controller.
Analog and digital inputs may be configured to report changes as they occur without being
polled by the Controller (report by exception). When the RTU recognizes an alarm condition,
it will check to see if the radio channel is busy. If the channel is busy, the RTU will wait for
the channel to clear. If the channel is not busy, the RTU will transmit its data and wait for a
reply from the Controller indicating that the alarm was received. If the RTU has not received
a reply within 15 seconds, it will re-send the packet and wait for a reply. In all cases, the
RTU will continue attempting to complete the transmission sequence until it receives the
correct response.
Each RTU can be configured differently so that the user can customize operation to match
the requirements of the application.
Содержание 1708
Страница 1: ...Models 1708 and 1716 Remote Terminal Units Installation and Operation Manual 025 9209K...
Страница 8: ...Contents 025 9209K 8...
Страница 56: ...025 9209K 56...
Страница 60: ...Repair 025 9209K 60 MODEL 1700 SERIES ENCLOSURE OUTLINE 024 0057B...
Страница 61: ...Repair 025 9209K 61 MODEL 1700 SERIES ENCLOSURE INSTRUCTIONS 024 0056D Sheet 1 of 2...
Страница 62: ...Repair 025 9209K 62 024 0056D Sheet 2 of 2...
Страница 63: ...Repair 025 9209K 63 MODEL 1708 REMOTE TERMINAL UNIT SILKSCREEN 702 9439F...
Страница 64: ...Repair 025 9209K 64 MODEL 1716 REMOTE TERMINAL UNIT SILKSCREEN 702 9440F...
Страница 72: ...Appendix B 025 9209K 72...
Страница 80: ...Glossary 025 9209K 80...