3. USER RESPONSIBILITIES & MAINTAINENCE OF THE FIRE ALARM SYSTEM, 

INCLUDING THE FACP & ITS INTEGRAL PSE 

According to the British Standard Code for Fire Detection and Alarm Systems for Commercial Buildings (

BS 5839-1

), the owner or 

person having control of the premises should appoint a responsible person to oversee the effective operation of the Fire Alarm 
System.  

Below is a summary of the main functions the “Responsible Person” is expected to carry out. This summary is not intended to 
replace Section seven (User responsibilities) of BS 5839-1 (available from BSI, or your local library). It is meant to give a brief outline 
of user responsibilities for the safe upkeep of the Fire Alarm System.  

The responsible person must:- 

1.

 

Have sufficient authority to carry out the duties associated with being the responsible person  

2.

 

Check the system at least once every 24 hours to ensure there are no faults present  

3.

 

Ensure there are arrangements for testing and maintaining the system  

4.

 

Ensure the log book is up to date, and available for inspection  

5.

 

Instruct all relevant occupants on the basic operation of the system, including start evacuation, silence alarms, silence 
faults and system reset 

6.

 

Take appropriate action to limit the rate of false alarms  

7.

 

Ensure that all detectors and manual call points remain unobstructed at all times  

8.

 

Liaise with maintenance personnel to ensure that cleaning, maintenance or building work does not interfere with the 
functioning and reliability of the fire alarm system 

9.

 

Ensure any changes to the system are recorded with updated drawings, operating instructions etc. 

10.

 

Ensure that there are spare parts (especially Call point elements) held on site  

11.

 

In the event of a pre-alarm, determine the cause & take appropriate action (predetermined fire routine if the cause is the 
start of a fire, arrange maintenance if the cause is a contaminated detector head)  

With the Smart Connect Fire Alarm Panel, we recommend the following tests are carried out: - 

Daily Inspection 

 

Check that the green Power LED is lit. 

 

If there are any yellow fault LEDs lit, or the green Power LED is not lit, report the fault(s) to the designated site 
maintenance engineer. 

Weekly Test (you may wish to temporarily disconnect the Aux relay during the following Tests) 

 

Set off a manual call point or sensor to test the Fire Alarm panel responds and all the sounders activate. 

 

Do not test the same device each week. Test a different zone each week using a different call point or detector so that 
eventually, all the devices will be tested. 

 

Enter user access code. Reset the System by pressing STOP SOUNDERS, SILENCE BUZZER, and RESET. 

 

Press the LED Test button. Check that all LEDs light, and the buzzer sounds 

 

Check that no call points or fire detectors are obstructed in any way. (e.g. New furniture or decorations) 

Quarterly Test (to be carried out by authorised service personnel only) 

 

Check that any servicing or repairs required by all previous logbook entries has been undertaken. 

 

Visual inspection of the batteries and connections. Check the alarm sounders work on battery only. 

 

Activate a device from each zone to test the fire alarm. (As per weekly test). 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание SmartConnect SMART1

Страница 1: ...Smart Connect Single loop touch screen panel 0 ONE LOOP TOUCH SCREEN ANALOGUE ADDRESSABLE FIRE ALARM PANEL USER MANUAL www acornfiresecurity com www acornfiresecurity com...

Страница 2: ...THE FIRE CONDITION 10 5 1 HOW THE SMART CONNECT INDICATES AN ALARM 10 5 2 HOW TO TURN OFF THE ALARM SOUNDERS 10 5 3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE 10 5 4 TURNING ON THE ALARM SOUNDERS...

Страница 3: ...opening a window If a fire is discovered either tackle it with fire extinguishers if suitably trained or call the fire brigade To reset the panel press the RESET button If the panel goes back into ala...

Страница 4: ...operating a Manual Call Point 3 To split the building into Zones each covering a different area of the building This will indicate which area of the system is giving the alarm or fault 4 To start its...

Страница 5: ...ioning and reliability of the fire alarm system 9 Ensure any changes to the system are recorded with updated drawings operating instructions etc 10 Ensure that there are spare parts especially Call po...

Страница 6: ...age 29 5 VAC Charger Voltage 27 3V off load adjusted with VR1 Battery Voltage 25 27V Every Five Years to be carried out by authorised service personnel only Carry out a complete wiring check in accord...

Страница 7: ...t LED and the Test LED respectively A zonal fault LED can be distinguished from disablement and test by the zonal fault LED flashing and the other two zonal conditions are indicated by a steady LED 4...

Страница 8: ...Connect Single loop touch screen panel Doc GLT 229 7 2 7 Issue 1 Date 11 03 2016 Main Menu Icons Sub menu tabs Numeric keypad Alpha keypad Scroll buttons www acornfiresecurity com www acornfiresecurit...

Страница 9: ...on the screen Putting the Panel into the Controls Enabled state see below ii CONTROLS ENABLED This access level is obtained by Selecting a user and entering the password for that user When the control...

Страница 10: ...ndications These are Common Fire Common Fault This light in conjunction with another LED which indicates the fire or fault condition as a backup indication They also include some specific indications...

Страница 11: ...e has been disabled it cannot be triggered into Alarm This should be remembered when disabling part of the system see Disablements in Section 7 5 2 HOW TO TURN OFF THE ALARM SOUNDERS The Alarm Sounder...

Страница 12: ...disabled pressing the STOP or START SOUNDERS BUTTON will have no effect 5 5 RESETTING THE PANEL Check the cause of the alarm activation If the cause of the alarm was an activated call point reset it...

Страница 13: ...ase It should be noted that any alarms raised on the fault zone s may not be recognised by the Fire Alarm Panel until the Fault Conditions have been cleared SYSTEM FAULT The System Fault LED lights wh...

Страница 14: ...e repeat the same procedure used for disabling the zone selecting Enable instead of Disable 7 3 TO DISABLE A POINT Rather than disable an entire zone it is often useful to just disable one or more inp...

Страница 15: ...ained in each zone NO OF DETECTORS NO OF MCPS NO OF SOUNDERS NO OF I OS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 SOUNDER CIRCUIT INFORMATION SOUNDER CIRCUIT SOUNDER CIRCUIT DESCRIPTION A brief descripti...

Страница 16: ...IVATED FIRE RELAY YES NO FAULT RELAY YES NO ADDITIONAL INFORMATION Any additional information the User needs to know about should be inserted into this box including details of the routing of any addi...

Страница 17: ...EL ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97 14 56 98 15 57 99 16 58 100 17 59 101 18 60 102...

Страница 18: ...7 220 135 178 221 136 179 222 137 180 223 138 181 224 139 182 225 140 183 226 141 184 227 142 185 228 143 186 229 144 187 230 145 188 231 146 189 232 147 190 233 148 191 234 149 192 235 150 193 236 15...

Страница 19: ...ns This LOG BOOK must be available for inspection at all times You can photocopy this log book to provide extra pages for when this book is full BS5839 part 1 recommends that fire alarm events should...

Страница 20: ...ch screen panel Doc GLT 229 7 2 19 Issue 1 Date 11 03 2016 MAINTENANCE WORK DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL WORK REQUIRED SIGNED www acornfiresecurity...

Страница 21: ...reen panel Doc GLT 229 7 2 20 Issue 1 Date 11 03 2016 MAINTENANCE WORK CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL WORK REQUIRED SIGNED www acornfiresecu...

Страница 22: ...e 11 03 2016 UNWANTED FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENAN CE FINDINGS CATEGORY OF FALSE ALARM FURTHER...

Страница 23: ...03 2016 UNWANTED FALSE ALARMS CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENAN CE FINDINGS CATEGORY OF FALSE ALARM FU...

Страница 24: ...7 2 23 Issue 1 Date 11 03 2016 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE IF KNOWN ACTION REQUIRED DATE COMPLETED INIT...

Страница 25: ...4 Issue 1 Date 11 03 2016 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE IF KNOWN ACTION REQUIRED DATE COMPLETED...

Страница 26: ...e correct zone and text message on the fire alarm panel The Sound pressure level throughout the building should be checked for compliance with the recommendations of BS5839 Pt1 Any deviations from BS5...

Страница 27: ...ies to the best of my our knowledge and belief with the recommendations of section 2 of BS 5839 1 for the system category described below except for the variations if any stated in this certificate Na...

Страница 28: ...e user to enable limitation of false alarms Other measures as follows INSTALLATION COMMISSIONING RECOMMENDATIONS It is strongly recommended that installation and commissioning be undertaken in accorda...

Страница 29: ...ons of BS5839 1 except for the variations if any stated in this certificate Name Block Letters Position Signature Date For on behalf of Address The extent of liability of the signatory is limited to t...

Страница 30: ...rectly Installation work is as far as can be reasonably ascertained of an acceptable standard The entire system has been inspected and tested in accordance with the recommendations of 39 2 c of BS 583...

Страница 31: ...ppears to be satisfactory The system is capable of giving a fire alarm signal The facility for remote transmission of alarms to an alarm receiving centre operates correctly Delete if not applicable Th...

Страница 32: ...en panel Doc GLT 229 7 2 31 Issue 1 Date 11 03 2016 User Manual Modification History Do Not Print This Page when creating PDF of the Manual ISSUE DATE CHANGES 1 11 03 2016 First draft www acornfiresec...

Отзывы: