5. THE FIRE CONDITION
5.1 HOW THE
Smart Connect
INDICATES AN ALARM
When the Panel is set into alarm by a Detector or
Manual Call Point located in a zone that is not already in
alarm it will: -
Light the COMMON FIRE LED and appropriate
ZONE FIRE LED(s) on the front of its enclosure.
Display fires from any zone on the LCD display.
Sound the Internal buzzer.
Start the Alarm Sounders and Auxiliary Outputs,
(unless a delay has been programmed).
The building evacuation procedure should now be
followed.
The LCD gives all the alarm information, such as the time & date of the alarm, the address, the device type, the device label, and the
zone it is allocated to.
IMPORTANT NOTE:
If a zone has been disabled, it cannot be triggered into Alarm. This should be remembered when disabling part
of the system. (see Disablements in Section 7).
5.2 HOW TO TURN OFF THE ALARM SOUNDERS
The Alarm Sounders may be silenced by entering the user code and momentarily pressing the STOP SOUNDERS button.
The Alarm Sounders will cease to sound* but the light(s) for the Zone(s) in Alarm and the red COMMON FIRE light will stay lit. The
Auxiliary Outputs will remain active. (The Panels internal buzzer can also be silenced by pressing the SILENCE BUZZER button).
5.3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE
If another detection Zone is activated after the Alarm Sounders have been silenced, the panel will: -
Restart the sounders (if the cause & effect has been configured to resound the sounders)
Light the Zone Fire LED(s) for any new Zone(s) in alarm
Keep the LED(s) for the previous Zone(s) in fire, and General Fire, lit.