background image

Smart Connect

 

Single loop touch screen panel

 

Doc: GLT-229-7-2 

 

 

 

 

 

 

 

 

 

 

 

12

 

Issue: 1 

Date: 11/03/2016 

 

 

 

 

 

6. THE FAULT CONDITION 

The fire alarm panel monitors itself, and any equipment connected to it, for any faults that can occur. If a fault occurs, the panel 
responds by activating its Internal buzzer and lighting the General Fault light and any other Fault light(s) relevant to the particular 
fault. The panel will also display the fault on its LCD display. The Panel’s Fault relay will also activate. If there is more than one fault, 
the MORE DATA LED will light. The user can either wait for each fault to be scrolled automatically on the LCD, or scroll manually 
through the list of faults using the up and down buttons. 

6.1 FAULT INDICATIONS 

The panel has the following yellow FAULT LEDs: 

 

COMMON FAULT, SYSTEM FAULT, SOUNDER 
FAULT/DISABLEMENT/TEST. 

 

 

 

There are 16 Zone LEDs which are used to indicate Zone Faults / 
Disablement / Test in Zones 1 – 16. (Conditions in zones 17 to 
254 are displayed on the LCD Screen) 

 

COMMON FAULT 

The Common fault LED is lit for all types of fault. 

ZONE FAULT 

The relevant Zone Fault light flashes when there is a wiring problem on a Zone or detector has been removed from its base. It 
should be noted that any alarms raised on the fault zone(s) may not be recognised by the Fire Alarm Panel until the Fault Conditions 
have been cleared.  

SYSTEM FAULT 

The System Fault LED lights when the Panel’s micro-processor has Reset, typically after excessive electrical interference, or if the 
contents of its memory have been corrupted. 

SOUNDER FAULT 

If there is a fault on the loop sounders, the line sounder fault LED will light along with the zone that contains that sounder. Because 
the sounder is addressable, any fault will be indicated as a device fault. 

6.2 WHAT TO DO IF A FAULT CONDITION OCCURS 

If a fault occurs, the responsible person should: 

 

Enter user access code and press the SILENCE BUZZER button. 

 

Write down the fault (s) in the Log Book at the back of this Manual. Take appropriate action to correct the fault (usually by 
contacting the service engineer). 

When a fault has been rectified the indicator light for that fault stays on until the RESET button is pressed. If the fault condition has 
not been rectified, the fault indication will only clear temporarily when the RESET button is pressed. 

Similarly, pressing the RESET button will clear the General Fault light (LED) and silence the Panel’s Internal Sounder (buzzer). If any 
fault(s) have not been rectified these will come back on again a short time later. 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание SmartConnect SMART1

Страница 1: ...Smart Connect Single loop touch screen panel 0 ONE LOOP TOUCH SCREEN ANALOGUE ADDRESSABLE FIRE ALARM PANEL USER MANUAL www acornfiresecurity com www acornfiresecurity com...

Страница 2: ...THE FIRE CONDITION 10 5 1 HOW THE SMART CONNECT INDICATES AN ALARM 10 5 2 HOW TO TURN OFF THE ALARM SOUNDERS 10 5 3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE 10 5 4 TURNING ON THE ALARM SOUNDERS...

Страница 3: ...opening a window If a fire is discovered either tackle it with fire extinguishers if suitably trained or call the fire brigade To reset the panel press the RESET button If the panel goes back into ala...

Страница 4: ...operating a Manual Call Point 3 To split the building into Zones each covering a different area of the building This will indicate which area of the system is giving the alarm or fault 4 To start its...

Страница 5: ...ioning and reliability of the fire alarm system 9 Ensure any changes to the system are recorded with updated drawings operating instructions etc 10 Ensure that there are spare parts especially Call po...

Страница 6: ...age 29 5 VAC Charger Voltage 27 3V off load adjusted with VR1 Battery Voltage 25 27V Every Five Years to be carried out by authorised service personnel only Carry out a complete wiring check in accord...

Страница 7: ...t LED and the Test LED respectively A zonal fault LED can be distinguished from disablement and test by the zonal fault LED flashing and the other two zonal conditions are indicated by a steady LED 4...

Страница 8: ...Connect Single loop touch screen panel Doc GLT 229 7 2 7 Issue 1 Date 11 03 2016 Main Menu Icons Sub menu tabs Numeric keypad Alpha keypad Scroll buttons www acornfiresecurity com www acornfiresecurit...

Страница 9: ...on the screen Putting the Panel into the Controls Enabled state see below ii CONTROLS ENABLED This access level is obtained by Selecting a user and entering the password for that user When the control...

Страница 10: ...ndications These are Common Fire Common Fault This light in conjunction with another LED which indicates the fire or fault condition as a backup indication They also include some specific indications...

Страница 11: ...e has been disabled it cannot be triggered into Alarm This should be remembered when disabling part of the system see Disablements in Section 7 5 2 HOW TO TURN OFF THE ALARM SOUNDERS The Alarm Sounder...

Страница 12: ...disabled pressing the STOP or START SOUNDERS BUTTON will have no effect 5 5 RESETTING THE PANEL Check the cause of the alarm activation If the cause of the alarm was an activated call point reset it...

Страница 13: ...ase It should be noted that any alarms raised on the fault zone s may not be recognised by the Fire Alarm Panel until the Fault Conditions have been cleared SYSTEM FAULT The System Fault LED lights wh...

Страница 14: ...e repeat the same procedure used for disabling the zone selecting Enable instead of Disable 7 3 TO DISABLE A POINT Rather than disable an entire zone it is often useful to just disable one or more inp...

Страница 15: ...ained in each zone NO OF DETECTORS NO OF MCPS NO OF SOUNDERS NO OF I OS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 SOUNDER CIRCUIT INFORMATION SOUNDER CIRCUIT SOUNDER CIRCUIT DESCRIPTION A brief descripti...

Страница 16: ...IVATED FIRE RELAY YES NO FAULT RELAY YES NO ADDITIONAL INFORMATION Any additional information the User needs to know about should be inserted into this box including details of the routing of any addi...

Страница 17: ...EL ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97 14 56 98 15 57 99 16 58 100 17 59 101 18 60 102...

Страница 18: ...7 220 135 178 221 136 179 222 137 180 223 138 181 224 139 182 225 140 183 226 141 184 227 142 185 228 143 186 229 144 187 230 145 188 231 146 189 232 147 190 233 148 191 234 149 192 235 150 193 236 15...

Страница 19: ...ns This LOG BOOK must be available for inspection at all times You can photocopy this log book to provide extra pages for when this book is full BS5839 part 1 recommends that fire alarm events should...

Страница 20: ...ch screen panel Doc GLT 229 7 2 19 Issue 1 Date 11 03 2016 MAINTENANCE WORK DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL WORK REQUIRED SIGNED www acornfiresecurity...

Страница 21: ...reen panel Doc GLT 229 7 2 20 Issue 1 Date 11 03 2016 MAINTENANCE WORK CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL WORK REQUIRED SIGNED www acornfiresecu...

Страница 22: ...e 11 03 2016 UNWANTED FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENAN CE FINDINGS CATEGORY OF FALSE ALARM FURTHER...

Страница 23: ...03 2016 UNWANTED FALSE ALARMS CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENAN CE FINDINGS CATEGORY OF FALSE ALARM FU...

Страница 24: ...7 2 23 Issue 1 Date 11 03 2016 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE IF KNOWN ACTION REQUIRED DATE COMPLETED INIT...

Страница 25: ...4 Issue 1 Date 11 03 2016 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE IF KNOWN ACTION REQUIRED DATE COMPLETED...

Страница 26: ...e correct zone and text message on the fire alarm panel The Sound pressure level throughout the building should be checked for compliance with the recommendations of BS5839 Pt1 Any deviations from BS5...

Страница 27: ...ies to the best of my our knowledge and belief with the recommendations of section 2 of BS 5839 1 for the system category described below except for the variations if any stated in this certificate Na...

Страница 28: ...e user to enable limitation of false alarms Other measures as follows INSTALLATION COMMISSIONING RECOMMENDATIONS It is strongly recommended that installation and commissioning be undertaken in accorda...

Страница 29: ...ons of BS5839 1 except for the variations if any stated in this certificate Name Block Letters Position Signature Date For on behalf of Address The extent of liability of the signatory is limited to t...

Страница 30: ...rectly Installation work is as far as can be reasonably ascertained of an acceptable standard The entire system has been inspected and tested in accordance with the recommendations of 39 2 c of BS 583...

Страница 31: ...ppears to be satisfactory The system is capable of giving a fire alarm signal The facility for remote transmission of alarms to an alarm receiving centre operates correctly Delete if not applicable Th...

Страница 32: ...en panel Doc GLT 229 7 2 31 Issue 1 Date 11 03 2016 User Manual Modification History Do Not Print This Page when creating PDF of the Manual ISSUE DATE CHANGES 1 11 03 2016 First draft www acornfiresec...

Отзывы: