background image

PREMIER QUATRO USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 

#Doc No. GLT.MAN-135 

 

PAGE 26

 

 

Issue: 1.05     Author: GW/NJ     Date: 24/07/2012

 

 

10. COMMISSIONING THE SYSTEM, INCLUDING POWER SUPPLY EQUIPMENT P.S.E. 

 

The commissioning of this fire alarm system should be performed by a qualified commissioning engineer, who has an 
understanding of sections 2, 3, & 4 of BS5839 pt 1:2002 (i.e. Design considerations, Limitations of false alarms, Installation 
recommendations). 

 

The system layout drawing should be checked for accuracy & stored in a safe place, accessible to any fire officer. 

 

The system set-up data chart (GLT.MAN-108, section 8) should be checked for accuracy. 

 

The fire alarm log book contact details should be checked for completeness. 

 

The insulation of cables should be checked in accordance with BS5839 Pt1: 2002 clause 38.2 for compliance. 

 

The Earthing should be checked in accordance with BS5839 Pt1: 2002 clause 38.2 for compliance. 

 

The PSE mains feed from a 3A spur should be checked. It should be protected by an over current device (MCB) NOT an 
earth leakage device (RCD). 

 

The PSE Charger voltage should be checked & adjusted if necessary (28.3 with batteries disconnected). 

 

The battery voltage should be checked (should be between 24 & 27V). 

 

All call points & detectors can signal an alarm condition and indicate the correct zone (and text message) on the fire alarm 
panel. 

 

The Sound pressure level throughout the building should be checked for compliance with the recommendations of 
BS5839 Pt1: 2002 clause 16.2. 

 

Any deviations from BS5839 Pt1 clause 7.2 should be listed in the Certificate of Installation & Commissioning. 

 

The Certificate of Installation & Commissioning should be completed, and the whole user manual passed to the relevant 
person on site. (They should be given a brief training on the basic operation of the FACP). 

10.1 DESIGN, INSTALLATION & COMMISSIONING CERTIFICATES 

The guidelines in BS 5839 Pt1: 2002 say that each stage of the system design and installation should have a separate certificate. 
Before this User Manual is handed over to the relevant person(s) on site, the following certificates (or the relevant company’s 
equivalent) should be completed by the system designer, the installation engineer and the commissioning engineer. The System 
Description sheet should also be completed on Pages 12-20 as should the relevant parts of the Log Book section starting on Page 21. 

The user or responsible person should then complete the acceptance certificate to acknowledge that they have been instructed in 
the use of the fire alarm, have witnessed that it is operational, and have been given all the relevant paperwork (drawings, log book, 
user manual, etc.). 

 

Содержание QT/1

Страница 1: ...L MAINTENANCE GUIDE LOG BOOK Software Versions PANEL 1 52 LOOP CARD 2 0 Doc No GLT MAN 135 Issue 1 05 Author GW NJ Date 24 07 2012 ONE TO FOUR LOOPS ANALOGUE ADDRESSABLE FIRE ALARM PANEL USER MANUAL M...

Страница 2: ...HOW THE QUATRO INDICATES AN ALARM 8 5 2 HOW TO TURN OFF THE ALARM SOUNDERS 8 5 3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE 8 5 4 TURNING ON THE ALARM SOUNDERS FROM THE FACP TO EVACUATE THE BUIL...

Страница 3: ...cessive dust etc can all activate a smoke detector If anything is found try to clear the room by opening a window If a fire is discovered either tackle it with fire extinguishers if suitably trained o...

Страница 4: ...be safely tackled or the local fire brigade called according to the company evacuation procedure 2 An Alarm can be raised from Smoke or Heat Detectors or manually by a person operating a Manual Call P...

Страница 5: ...aintenance personnel to ensure that cleaning maintenance or building work does not interfere with the functioning and reliability of the fire alarm system 47 2 h 9 Ensure any changes to the system are...

Страница 6: ...operation Check Switch Mode cage INPUT Voltage 30 5 VAC Charger Voltage 27 6V off load adjusted with VR1 Battery Voltage 25 27V Every Five Years to be carried out by authorised service personnel only...

Страница 7: ...lock If the panel is located in a position where the general public have access this key must be removed from the panel and placed where it can be easily accessed by authorised personnel only The acce...

Страница 8: ...LEDs and LCD The user can also enter the test mode which permits points in selected zone s to be tested without causing the alarm to be raised throughout the building iv INSTALLER MENU FOR INSTALLATI...

Страница 9: ...urred in zone 25 The 2nd point is located in zone 86 STAIRWELL The address label of this point is ROOM 101 It is on panel number 2 loop number 4 and at address 124 The point which is an optical detect...

Страница 10: ...ence the Alarm Sounders Note If ALL of the Alarm Sounders have been disabled pressing the STOP START BUTTON will have no effect 5 5 RESETTING THE PANEL Check the cause of the alarm activation If the c...

Страница 11: ...ULTS To the left of this are 20 LEDs which are used to indicate Zone Faults Disablement Test in Zones 1 20 COMMON FAULT The Common fault LED is lit for all types of fault SUPPLY FAULT This indicates a...

Страница 12: ...ault LED will light along with the zone that contains that sounder Because the sounder is addressable any fault will be indicated as a device fault 6 2 WHAT TO DO IF A FAULT CONDITION OCCURS If a faul...

Страница 13: ...at the same procedure used for disabling the zone selecting Enable instead of Disable 7 3 TO DISABLE A POINT Rather than disable an entire zone it is often useful to just disable one or more input dev...

Страница 14: ...l the rooms and areas contained in each zone NO OF DETECTORS NO OF MCPS NO OF SOUNDERS NO OF I OS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 SOUNDER CIRCUIT INFORMATION SOUNDER CIRCUIT SOUNDER...

Страница 15: ...E OF OUTPUT CONNECTED WHAT HAPPENS WHEN ACTIVATED FIRE RELAY YES NO FAULT RELAY YES NO ADDITIONAL INFORMATION Any additional information the User needs to know about should be inserted into this box i...

Страница 16: ...ware will also be acceptable ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97...

Страница 17: ...ware will also be acceptable ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97...

Страница 18: ...ware will also be acceptable ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97...

Страница 19: ...ware will also be acceptable ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97...

Страница 20: ...of any outstanding work or panel conditions This LOG BOOK must be available for inspection at all times You can photocopy this log book to provide extra pages for when this book is full BS5839 part 1...

Страница 21: ...MANUAL MAINTENANCE GUIDE LOG BOOK Doc No GLT MAN 135 PAGE 20 Issue 1 05 Author GW NJ Date 24 07 2012 MAINTENANCE WORK DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL W...

Страница 22: ...L MAINTENANCE GUIDE LOG BOOK Doc No GLT MAN 135 PAGE 21 Issue 1 05 Author GW NJ Date 24 07 2012 MAINTENANCE WORK CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIO...

Страница 23: ...AN 135 PAGE 22 Issue 1 05 Author GW NJ Date 24 07 2012 UNWANTED FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENAN C...

Страница 24: ...5 PAGE 23 Issue 1 05 Author GW NJ Date 24 07 2012 UNWANTED FALSE ALARMS CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTE...

Страница 25: ...G BOOK Doc No GLT MAN 135 PAGE 24 Issue 1 05 Author GW NJ Date 24 07 2012 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE I...

Страница 26: ...K Doc No GLT MAN 135 PAGE 25 Issue 1 05 Author GW NJ Date 24 07 2012 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION DETAILS OF EVENT INCLUDING CA...

Страница 27: ...call points detectors can signal an alarm condition and indicate the correct zone and text message on the fire alarm panel The Sound pressure level throughout the building should be checked for compli...

Страница 28: ...I we have been responsible complies to the best of my our knowledge and belief with the recommendations of section 2 of BS 5839 1 2002 for the system category described below except for the variation...

Страница 29: ...ance has been provided to the user to enable limitation of false alarms Other measures as follows INSTALLATION COMMISSIONING RECOMMENDATIONS It is strongly recommended that installation and commission...

Страница 30: ...d below and with the recommendations of BS5839 1 2002 except for the variations if any stated in this certificate Name Block Letters Position Signature Date For on behalf of Address The extent of liab...

Страница 31: ...clause 7 All equipment operates correctly Installation work is as far as can be reasonably ascertained of an acceptable standard The entire system has been inspected and tested in accordance with the...

Страница 32: ...this certificate All installation work appears to be satisfactory The system is capable of giving a fire alarm signal The facility for remote transmission of alarms to an alarm receiving centre opera...

Отзывы: