PREMIER QUATRO USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 

#Doc No. GLT.MAN-135 

 

PAGE 28

 

 

Issue: 1.05     Author: GW/NJ     Date: 24/07/2012

 

 

Design Certificate 

(Page 2 of 2) 

 
Measures incorporated to limit false alarms. Account has to be taken of the guidance contained in section 3 
of BS 5839-1: 2002 and, more specifically (tick as appropriate): 

 

 The System is manual. Type & siting of manual call points takes account of the guidelines contained in 

section 3 of BS 5839-1 

 The system incorporates automatic fire detectors, and account has been taken of reasonably foreseeable 

causes of unwanted alarms, particularly in the selection and siting of detectors 

 An appropriate analogue system has been specified 
 An appropriate multi-sensor system has been specified 
 A time-related system has been specified. Details:  

 
 
 
 

 Fire signals from automatic fire detectors result initially in a staff alarm, which delays a  general alarm / 

transmission of signals to an alarm receiving centre (delete as applicable) for             min. 

 Appropriate guidance has been provided to the user to enable limitation of false alarms. 
 Other measures as follows:  

 
 
 

INSTALLATION & COMMISSIONING RECOMMENDATIONS 

It is strongly recommended that installation and commissioning be undertaken in accordance with the 
recommendations of section 4 and section 5 of BS 5839-1: 2002 respectively. 
 

SOAK TEST 

 In accordance with the recommendations of clause 35.2.6 of BS 5839-1:2002, it is recommended   that 

following commissioning a soak period of                            should follow. 
(enter a period of at least 1 week) 
 

 As the system incorporates no more than 50 automatic fire detectors, no soak test is necessary to satisfy 

the recommendations of BS 5839-1:2002 
 

VERIFICATION 

Verification that the system complies with BS 5839-1:2002 should be carried out, on completion, in 
accordance with BS 5839-1:2002 Clause 43 

 Yes 

No 

 To be decided by the purchaser or user 

 

MAINTENANCE 

It is strongly recommended that, after completion, the system is maintained in accordance with section 6 of 
BS 5839-1:2002 
 

USER RESPONSIBILITIES 

The user should appoint a responsible person to supervise all matters pertaining to the fire alarm system in 
accordance with the recommendations of section 7 of BS 5839-1:2002 
 

Содержание QT/1

Страница 1: ...L MAINTENANCE GUIDE LOG BOOK Software Versions PANEL 1 52 LOOP CARD 2 0 Doc No GLT MAN 135 Issue 1 05 Author GW NJ Date 24 07 2012 ONE TO FOUR LOOPS ANALOGUE ADDRESSABLE FIRE ALARM PANEL USER MANUAL M...

Страница 2: ...HOW THE QUATRO INDICATES AN ALARM 8 5 2 HOW TO TURN OFF THE ALARM SOUNDERS 8 5 3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE 8 5 4 TURNING ON THE ALARM SOUNDERS FROM THE FACP TO EVACUATE THE BUIL...

Страница 3: ...cessive dust etc can all activate a smoke detector If anything is found try to clear the room by opening a window If a fire is discovered either tackle it with fire extinguishers if suitably trained o...

Страница 4: ...be safely tackled or the local fire brigade called according to the company evacuation procedure 2 An Alarm can be raised from Smoke or Heat Detectors or manually by a person operating a Manual Call P...

Страница 5: ...aintenance personnel to ensure that cleaning maintenance or building work does not interfere with the functioning and reliability of the fire alarm system 47 2 h 9 Ensure any changes to the system are...

Страница 6: ...operation Check Switch Mode cage INPUT Voltage 30 5 VAC Charger Voltage 27 6V off load adjusted with VR1 Battery Voltage 25 27V Every Five Years to be carried out by authorised service personnel only...

Страница 7: ...lock If the panel is located in a position where the general public have access this key must be removed from the panel and placed where it can be easily accessed by authorised personnel only The acce...

Страница 8: ...LEDs and LCD The user can also enter the test mode which permits points in selected zone s to be tested without causing the alarm to be raised throughout the building iv INSTALLER MENU FOR INSTALLATI...

Страница 9: ...urred in zone 25 The 2nd point is located in zone 86 STAIRWELL The address label of this point is ROOM 101 It is on panel number 2 loop number 4 and at address 124 The point which is an optical detect...

Страница 10: ...ence the Alarm Sounders Note If ALL of the Alarm Sounders have been disabled pressing the STOP START BUTTON will have no effect 5 5 RESETTING THE PANEL Check the cause of the alarm activation If the c...

Страница 11: ...ULTS To the left of this are 20 LEDs which are used to indicate Zone Faults Disablement Test in Zones 1 20 COMMON FAULT The Common fault LED is lit for all types of fault SUPPLY FAULT This indicates a...

Страница 12: ...ault LED will light along with the zone that contains that sounder Because the sounder is addressable any fault will be indicated as a device fault 6 2 WHAT TO DO IF A FAULT CONDITION OCCURS If a faul...

Страница 13: ...at the same procedure used for disabling the zone selecting Enable instead of Disable 7 3 TO DISABLE A POINT Rather than disable an entire zone it is often useful to just disable one or more input dev...

Страница 14: ...l the rooms and areas contained in each zone NO OF DETECTORS NO OF MCPS NO OF SOUNDERS NO OF I OS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 SOUNDER CIRCUIT INFORMATION SOUNDER CIRCUIT SOUNDER...

Страница 15: ...E OF OUTPUT CONNECTED WHAT HAPPENS WHEN ACTIVATED FIRE RELAY YES NO FAULT RELAY YES NO ADDITIONAL INFORMATION Any additional information the User needs to know about should be inserted into this box i...

Страница 16: ...ware will also be acceptable ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97...

Страница 17: ...ware will also be acceptable ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97...

Страница 18: ...ware will also be acceptable ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97...

Страница 19: ...ware will also be acceptable ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97...

Страница 20: ...of any outstanding work or panel conditions This LOG BOOK must be available for inspection at all times You can photocopy this log book to provide extra pages for when this book is full BS5839 part 1...

Страница 21: ...MANUAL MAINTENANCE GUIDE LOG BOOK Doc No GLT MAN 135 PAGE 20 Issue 1 05 Author GW NJ Date 24 07 2012 MAINTENANCE WORK DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL W...

Страница 22: ...L MAINTENANCE GUIDE LOG BOOK Doc No GLT MAN 135 PAGE 21 Issue 1 05 Author GW NJ Date 24 07 2012 MAINTENANCE WORK CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIO...

Страница 23: ...AN 135 PAGE 22 Issue 1 05 Author GW NJ Date 24 07 2012 UNWANTED FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENAN C...

Страница 24: ...5 PAGE 23 Issue 1 05 Author GW NJ Date 24 07 2012 UNWANTED FALSE ALARMS CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTE...

Страница 25: ...G BOOK Doc No GLT MAN 135 PAGE 24 Issue 1 05 Author GW NJ Date 24 07 2012 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE I...

Страница 26: ...K Doc No GLT MAN 135 PAGE 25 Issue 1 05 Author GW NJ Date 24 07 2012 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION DETAILS OF EVENT INCLUDING CA...

Страница 27: ...call points detectors can signal an alarm condition and indicate the correct zone and text message on the fire alarm panel The Sound pressure level throughout the building should be checked for compli...

Страница 28: ...I we have been responsible complies to the best of my our knowledge and belief with the recommendations of section 2 of BS 5839 1 2002 for the system category described below except for the variation...

Страница 29: ...ance has been provided to the user to enable limitation of false alarms Other measures as follows INSTALLATION COMMISSIONING RECOMMENDATIONS It is strongly recommended that installation and commission...

Страница 30: ...d below and with the recommendations of BS5839 1 2002 except for the variations if any stated in this certificate Name Block Letters Position Signature Date For on behalf of Address The extent of liab...

Страница 31: ...clause 7 All equipment operates correctly Installation work is as far as can be reasonably ascertained of an acceptable standard The entire system has been inspected and tested in accordance with the...

Страница 32: ...this certificate All installation work appears to be satisfactory The system is capable of giving a fire alarm signal The facility for remote transmission of alarms to an alarm receiving centre opera...

Отзывы: