background image

PREMIER QUATRO USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 

#Doc No. GLT.MAN-135 

 

PAGE 4

 

 

Issue: 1.05     Author: GW/NJ     Date: 24/07/2012

 

 

3. USER RESPONSIBILITIES & MAINTAINENCE OF THE FIRE ALARM SYSTEM, 

INCLUDING THE FACP & ITS INTEGRAL PSE 

According to the British Standard Code for Fire Detection and Alarm Systems for Commercial Buildings (

BS 5839-1

:2002+A2:2008), 

the owner or person having control of the premises should appoint a responsible person to oversee the effective operation of the 
Fire Alarm System (Clause 47.1). 

Below is a summary of the main functions the “Responsible Person” is expected to carry out. This summary is not intended to 
replace Section seven (User responsibilities) of BS 5839-1:2002+A2:2008 (available from BSI, or your local library). It is meant to give 
a brief outline of user responsibilities for the safe upkeep of the Fire Alarm System. The number in brackets shows the relevant 
BS5839: Pt 1: 2002 clauses. 

The responsible person must:- 

1.

 

Have sufficient authority to carry out the duties associated with being the responsible person (47.2.a) 

2.

 

Check the system at least once every 24 hours to ensure there are no faults present (47.2.b) 

3.

 

Ensure there are arrangements for testing and maintaining the system (47.2.c) 

4.

 

Ensure the log book is up to date, and available for inspection (47.2.d) 

5.

 

Instruct all relevant occupants on the basic operation of the system, including start evacuation, silence alarms, silence 
faults and system reset (47.2.e) 

6.

 

Take appropriate action to limit the rate of false alarms (47.2.f) 

7.

 

Ensure that all detectors and manual call points remain unobstructed at all times (47.2.g) 

8.

 

Liaise with maintenance personnel to ensure that cleaning, maintenance or building work does not interfere with the 
functioning and reliability of the fire alarm system (47.2.h). 

9.

 

Ensure any changes to the system are recorded with updated drawings, operating instructions etc. (47.2.i) 

10.

 

Ensure that there are spare parts (especially Call point elements) held on site (47.2.j.1&2) 

11.

 

In the event of a pre-alarm, determine the cause & take appropriate action (predetermined fire routine if the cause is the 
start of a fire, arrange maintenance if the cause is a contaminated detector head) (47.3)  

With the Quatro Fire Alarm Panel, we recommend the following tests are carried out: - 

Daily Inspection 

 

Check that the green Power LED is lit. 

 

If there are any yellow fault LEDs lit, or the green Power LED is not lit, report the fault(s) to the designated site 
maintenance engineer. 

Weekly Test (you may wish to temporarily disconnect the Aux relay during the following Tests) 

 

Set off a manual call point or sensor to test the Fire Alarm panel responds and all the sounders activate. 

 

Do not test the same device each week. Test a different zone each week using a different call point or detector so that 
eventually, all the devices will be tested. 

 

Turn key to CONTROLS ENABLED. Reset the System by pressing STOP SOUNDERS, SILENCE BUZZER, RESET. 

 

Press the LED Test button. Check that all LEDs light, and the buzzer sounds 

 

Check that no call points or fire detectors are obstructed in any way. (e.g. New furniture or decorations) 

Quarterly Test (to be carried out by authorised service personnel only) 

 

Check that any servicing or repairs required by all previous logbook entries has been undertaken. 

 

Visual inspection of the batteries and connections. Check the alarm sounders work on battery only. 

 

Activate a device from each zone to test the fire alarm. (As per weekly test). 

Содержание QT/1

Страница 1: ...L MAINTENANCE GUIDE LOG BOOK Software Versions PANEL 1 52 LOOP CARD 2 0 Doc No GLT MAN 135 Issue 1 05 Author GW NJ Date 24 07 2012 ONE TO FOUR LOOPS ANALOGUE ADDRESSABLE FIRE ALARM PANEL USER MANUAL M...

Страница 2: ...HOW THE QUATRO INDICATES AN ALARM 8 5 2 HOW TO TURN OFF THE ALARM SOUNDERS 8 5 3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE 8 5 4 TURNING ON THE ALARM SOUNDERS FROM THE FACP TO EVACUATE THE BUIL...

Страница 3: ...cessive dust etc can all activate a smoke detector If anything is found try to clear the room by opening a window If a fire is discovered either tackle it with fire extinguishers if suitably trained o...

Страница 4: ...be safely tackled or the local fire brigade called according to the company evacuation procedure 2 An Alarm can be raised from Smoke or Heat Detectors or manually by a person operating a Manual Call P...

Страница 5: ...aintenance personnel to ensure that cleaning maintenance or building work does not interfere with the functioning and reliability of the fire alarm system 47 2 h 9 Ensure any changes to the system are...

Страница 6: ...operation Check Switch Mode cage INPUT Voltage 30 5 VAC Charger Voltage 27 6V off load adjusted with VR1 Battery Voltage 25 27V Every Five Years to be carried out by authorised service personnel only...

Страница 7: ...lock If the panel is located in a position where the general public have access this key must be removed from the panel and placed where it can be easily accessed by authorised personnel only The acce...

Страница 8: ...LEDs and LCD The user can also enter the test mode which permits points in selected zone s to be tested without causing the alarm to be raised throughout the building iv INSTALLER MENU FOR INSTALLATI...

Страница 9: ...urred in zone 25 The 2nd point is located in zone 86 STAIRWELL The address label of this point is ROOM 101 It is on panel number 2 loop number 4 and at address 124 The point which is an optical detect...

Страница 10: ...ence the Alarm Sounders Note If ALL of the Alarm Sounders have been disabled pressing the STOP START BUTTON will have no effect 5 5 RESETTING THE PANEL Check the cause of the alarm activation If the c...

Страница 11: ...ULTS To the left of this are 20 LEDs which are used to indicate Zone Faults Disablement Test in Zones 1 20 COMMON FAULT The Common fault LED is lit for all types of fault SUPPLY FAULT This indicates a...

Страница 12: ...ault LED will light along with the zone that contains that sounder Because the sounder is addressable any fault will be indicated as a device fault 6 2 WHAT TO DO IF A FAULT CONDITION OCCURS If a faul...

Страница 13: ...at the same procedure used for disabling the zone selecting Enable instead of Disable 7 3 TO DISABLE A POINT Rather than disable an entire zone it is often useful to just disable one or more input dev...

Страница 14: ...l the rooms and areas contained in each zone NO OF DETECTORS NO OF MCPS NO OF SOUNDERS NO OF I OS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 SOUNDER CIRCUIT INFORMATION SOUNDER CIRCUIT SOUNDER...

Страница 15: ...E OF OUTPUT CONNECTED WHAT HAPPENS WHEN ACTIVATED FIRE RELAY YES NO FAULT RELAY YES NO ADDITIONAL INFORMATION Any additional information the User needs to know about should be inserted into this box i...

Страница 16: ...ware will also be acceptable ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97...

Страница 17: ...ware will also be acceptable ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97...

Страница 18: ...ware will also be acceptable ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97...

Страница 19: ...ware will also be acceptable ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97...

Страница 20: ...of any outstanding work or panel conditions This LOG BOOK must be available for inspection at all times You can photocopy this log book to provide extra pages for when this book is full BS5839 part 1...

Страница 21: ...MANUAL MAINTENANCE GUIDE LOG BOOK Doc No GLT MAN 135 PAGE 20 Issue 1 05 Author GW NJ Date 24 07 2012 MAINTENANCE WORK DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL W...

Страница 22: ...L MAINTENANCE GUIDE LOG BOOK Doc No GLT MAN 135 PAGE 21 Issue 1 05 Author GW NJ Date 24 07 2012 MAINTENANCE WORK CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIO...

Страница 23: ...AN 135 PAGE 22 Issue 1 05 Author GW NJ Date 24 07 2012 UNWANTED FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENAN C...

Страница 24: ...5 PAGE 23 Issue 1 05 Author GW NJ Date 24 07 2012 UNWANTED FALSE ALARMS CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTE...

Страница 25: ...G BOOK Doc No GLT MAN 135 PAGE 24 Issue 1 05 Author GW NJ Date 24 07 2012 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE I...

Страница 26: ...K Doc No GLT MAN 135 PAGE 25 Issue 1 05 Author GW NJ Date 24 07 2012 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION DETAILS OF EVENT INCLUDING CA...

Страница 27: ...call points detectors can signal an alarm condition and indicate the correct zone and text message on the fire alarm panel The Sound pressure level throughout the building should be checked for compli...

Страница 28: ...I we have been responsible complies to the best of my our knowledge and belief with the recommendations of section 2 of BS 5839 1 2002 for the system category described below except for the variation...

Страница 29: ...ance has been provided to the user to enable limitation of false alarms Other measures as follows INSTALLATION COMMISSIONING RECOMMENDATIONS It is strongly recommended that installation and commission...

Страница 30: ...d below and with the recommendations of BS5839 1 2002 except for the variations if any stated in this certificate Name Block Letters Position Signature Date For on behalf of Address The extent of liab...

Страница 31: ...clause 7 All equipment operates correctly Installation work is as far as can be reasonably ascertained of an acceptable standard The entire system has been inspected and tested in accordance with the...

Страница 32: ...this certificate All installation work appears to be satisfactory The system is capable of giving a fire alarm signal The facility for remote transmission of alarms to an alarm receiving centre opera...

Отзывы: