background image

PREMIER M PLUS INSTALLATION MANUAL 

Approved Document No: GLT.MAN-111 

 

PAGE 

6

 

Issue : 2.8 Author: NJ Date: 23/07/2012 

Old Manual call points, which just cause a short circuit, are not 
directly compatible, as they would cause a short circuit fault. 
Fitting a 470R resistor in line with the call point will allow it to 
work.  
 
(Note: if this is the last device, the end of line (+ve) will connect to 
the connector block, NOT the call point) 

 

 
Other makes of detector will have different connections, but in general they are wired in one of 2 ways: 

SPLIT NEGATIVE 

+IN

 & 

+OUT

 to same terminal, 

-IN

 to stripe side of continuity diode, 

-OUT

 to non-stripe side of continuity diode. 

Or 

SPLIT POSITIVE 

+IN

 to non-stripe side of continuity diode, 

+OUT

 to stripe side of continuity diode, 

-IN

 & 

-OUT

 to same terminal. 

Some makes of detector will connect the +ve to a 470R load resistor, or a polarisation diode, to enable the detector to work 
correctly with European Fire Alarm Panels. 

For more specific device wiring information, please refer to the device manufacturers' own instructions. 

The termination of each detection circuit must be as indicated on the main PCB (See page 15). The Earthing of the cable screens 
should be as shown on page 9. 

3.4 SOUNDER CIRCUIT WIRING DIAGRAM 

 

 

Note: If non-polarised alarm devices (e.g. some types of old mechanical bell, or a relay) are used, then a diode will have to be placed 
in line with the device to enable fault monitoring. They may also need a back EMF protection diode. (symptoms: Chattering sounder 
relays that don’t turn off). 

3.5 AUXILIARY OUTPUT WIRING 

3.5.1 Auxiliary Fire Output (AUX): 

Voltage free changeover contacts. Changes over in any fire condition, and is used for driving local fire fighting equipment such as 
sprinkler systems, magnetic door holders, air conditioning shut off, etc. 

Содержание Premier M plus

Страница 1: ...PREMIER M PLUS INSTALLATION MANUAL Approved Document No GLT MAN 111 Issue 2 8 Author NJ Date 23 07 2012 8 24 ZONE CONVENTIONAL FIRE ALARM PANEL INSTALLATION MANUAL...

Страница 2: ...Its Features include Designed to EN54 Parts 2 4 It is available in 8 16 or 24 zones sizes Automatically uses diode bases for line continuity Four common sounder circuits 400mA Each Serial Repeater Ou...

Страница 3: ...ERY POWER 9 5 1 CONNECTING THE MAINS POWER 9 5 2 CONNECTING THE BATTERIES 9 6 FIELD DEVICE TERMINATION 10 6 1 TERMINATING THE DETECTION AND ALARM SOUNDER CIRCUITS 10 6 2 AUXILIARY INPUT AND OUTPUT TER...

Страница 4: ...void damage by static The best method is to wear an earth strap but touching any earth point e g building plumbing will help to discharge any static Always handle PCBs by their sides and avoid touchin...

Страница 5: ...ply with a supply rating IMAX of 5 0 Amps The PSE has a 920mA limited charger output 2 3 ENVIRONMENTAL It will operate in ambient temperatures of 5 to 40 o C It will operate in a relative humidity of...

Страница 6: ...BS5839 installations other cable types may be suitable Depending on the environment the cables may need mechanical protection such as a conduit 3 2 MAINS WIRING RECOMMENDATIONS The Mains supply to the...

Страница 7: ...ector will connect the ve to a 470R load resistor or a polarisation diode to enable the detector to work correctly with European Fire Alarm Panels For more specific device wiring information please re...

Страница 8: ...dition to a larger addressable fire alarm system 3 5 3 Fire Alarm Routing Equipment Output F A R E Monitored 24V nominal output This is a 24V 100mA output that activates in any fire condition and is u...

Страница 9: ...el box If a grommet is removed fill the hole with a brass cable gland If any knockout is removed but subsequently not used it should be covered up The 230Va c Mains cable must be fed into the enclosur...

Страница 10: ...to apply power to the panel before connecting any devices to check for correct operation and to familiarise yourself with the fire alarm panels controls 5 2 CONNECTING THE BATTERIES Figure 4 Battery...

Страница 11: ...to the appropriate connector block on the Termination PCB as shown in Figure 6 below For detailed detection and alarm circuit wiring diagrams please refer to pages 6 and 7 Figure 6 Detector and Sound...

Страница 12: ...TTING EXTERNAL SOUNDER DELAY IN MINUTES e g The above example would have a delay of 1 minute 0 No Delay 1 1 Minute 2 2 Minutes 3 3 Minutes 4 4 Minutes 5 5 Minutes 6 6 Minutes 7 7 Minutes 8 8 Minutes 9...

Страница 13: ...lit The item that has been disabled will now flash 3 quick flashes then on This means that it has been disabled but is still the focus of the disablement select de select operation If scroll is presse...

Страница 14: ...PROGRAMME ZONE IN TEST NOTE Only one zone can be programmed in test at any one time 1 Insert and turn control key to enabled position 2 Press FUNCTION button twice The General Zone test LED is now on...

Страница 15: ...ible with this FACP Note that some makes of detector will require a series resistor or diode to be fitted to work properly There is usually a spare connector on the base to accommodate this check inst...

Страница 16: ...fault The recommended setting it to monitor via the motherboard 10 5 SOUNDER FAULTS Check that the correct END of Line resistor has been fitted 10K brown black orange gold Check that all sounder fuse...

Страница 17: ...The required standby is 24 hours It will need to operate in alarm for hour Calculate the battery size required TALM 0 5 Hr IALM panel 0 205mA IALM 4x10 x 0 025 1 0A This typical bell current is 25 mA...

Страница 18: ...including test mode 6 FAULT RELAY NO CM NC Activates on fault 7 F A R E FIRE ALARM ROUTING EQUIPMENT 8 SND 1 Connect to sounder circuit 1 sirens bells 9 SND 2 Connect to sounder circuit 2 sirens bell...

Страница 19: ...Date 23 07 2012 FS5 Sounder circuit 2 400mA time delay 5 x 20mm glass FS6 AUX Supply 250mA time delay 5 x 20mm glass FS7 Sounder circuit 3 400mA time delay 5 x 20mm glass FS8 Sounder circuit 4 400mA t...

Страница 20: ...utput 6 B FUSE Fuse for the second 24V output 7 BATTERY Battery connection 2 x 12V SLA batteries wired in series 8 FACTORY ADJUST Charger adjust pot DO NOT ADJUST 9 THERM Battery charger temperature c...

Страница 21: ...IRCUIT Determined by momentatily reversing the zone voltage SOUNDER ALARM OUTPUTS 4 x 400mA 29V DC Nominal Min 18 9V DC Max 31 9V DC AUXILIARY FAULT OUTPUT 1 x RELAY SELV 1A MAX AUXILIARY FIRE OUTPUT...

Страница 22: ...a SA1 2EN 12 0359 CPD 0143 EN54 2 1997 A1 2002 A2 2006 EN54 4 1997 A1 2002 A2 2006 Control and indicating equipment for fire detection and fire alarm systems for buildings PMP8 PMP16 PMP24 Provided op...

Отзывы: