background image

PREMIER M PLUS INSTALLATION MANUAL 

Approved Document No: GLT.MAN-111 

 

PAGE 

20

 

Issue : 2.8 Author: NJ Date: 23/07/2012 

13. PANEL SPECIFICATIONS 

13.1 ENCLOSURE SPECIFICATIONS 

DESCRIPTION 

VALUE 

ENCLOSURE SIZE 

485 X 478 X 125mm 

TOP CABLE ENTRIES 

20 X 19mm DIA GROMMETED ENTRIES 

BOTTOM CABLE ENTRIES 

6 X 19mm DIA GROMMETED ENTRIES 

REAR CABLE ENTRIES 

N/A 

13.2 ELECTRICAL SPECIFICATIONS 

ELECTRICAL DESCRIPTION 

VALUE 

MAINS VOLTAGE 

230V AC +/- 10% @ 50/60 Hz 

BATTERY VOLTAGE 

24V DC (2 X 12V SLA BATTERY) 

SYSTEM VOLTAGE 

28V DC NOMINAL (19V to 32 V) 

SYSTEM VOLTAGE RIPPLE 

2V PK-PK MAX 

CHARGER SIZE 

UP TO 17AH in 24 Hours 

ZONE VOLTAGE 

21V DC (NOMINAL): Min 17V DC, Max 31.9V DC (17 - 22.5V) 

ZONE ALARM TRIGGERING CURRENT 

Min 20mA, Max 100mA 

ZONE SHORT CIRCUIT CURRENT 

>100mA 

ZONE OPEN CIRCUIT 

Determined by momentatily reversing the zone voltage 

SOUNDER ALARM OUTPUTS 

4 x 400mA @ 29V DC (Nominal) : Min 18.9V DC, Max 31.9V DC 

AUXILIARY FAULT OUTPUT 

1 x RELAY SELV (1A MAX) 

AUXILIARY FIRE OUTPUT 

1 x RELAY SELV (1A MAX) 

F.A.R.E. OUTPUT 

1 X 100mA @ 29V DC : Min 17.2V DC, Max 30.1V DC 

NUMBER OF ZONES 

8/16/24 

MAXIMUM ZONE CAPACITY 

32 DEVICES PER ZONE 

MAXIMUM ZONE CABLE RESISTANCE 

70 ohms 

AUXILIARY SUPPLY 

250mA @ 29 V DC (NOMINAL) : Min 18.9V DC, Max 31.9V DC 

SOUNDER ACTIVATION DELAY 

0-9 MINUTES -IN 1 MIN INCREMENTS 

ZONE END OF LINE DEVICE 

1N4002 DIODE (STRIPE TO POSITIVE) 

SOUNDER END OF LINE DEVICE 

10 K RESISTOR 

CHARGER VOLTAGE 

27.6V @ 25

o

C (NO BATTERY CONNECTED) 

BATTERY DEEP DISCHARGE PROTECTION 

Batteries less than 20.5V 

MAXIMUM ALLOWED BATTERY INTERNAL RESISTANCE 

0.9 Ω 

TOTAL PSU OUTPUT 

5 Amp 

MAXIMUM CHARGING CURRENT 

920mA 

 

 

PANEL LOAD FOR BATTERY CALCULATIONS 

VALUE 

PANEL CURRENT IN MAINS FAIL 

105mA (85 mA with buzzer silenced) 

PANEL CURRENT IN ALARM 

205mA 

 

 

Содержание Premier M plus

Страница 1: ...PREMIER M PLUS INSTALLATION MANUAL Approved Document No GLT MAN 111 Issue 2 8 Author NJ Date 23 07 2012 8 24 ZONE CONVENTIONAL FIRE ALARM PANEL INSTALLATION MANUAL...

Страница 2: ...Its Features include Designed to EN54 Parts 2 4 It is available in 8 16 or 24 zones sizes Automatically uses diode bases for line continuity Four common sounder circuits 400mA Each Serial Repeater Ou...

Страница 3: ...ERY POWER 9 5 1 CONNECTING THE MAINS POWER 9 5 2 CONNECTING THE BATTERIES 9 6 FIELD DEVICE TERMINATION 10 6 1 TERMINATING THE DETECTION AND ALARM SOUNDER CIRCUITS 10 6 2 AUXILIARY INPUT AND OUTPUT TER...

Страница 4: ...void damage by static The best method is to wear an earth strap but touching any earth point e g building plumbing will help to discharge any static Always handle PCBs by their sides and avoid touchin...

Страница 5: ...ply with a supply rating IMAX of 5 0 Amps The PSE has a 920mA limited charger output 2 3 ENVIRONMENTAL It will operate in ambient temperatures of 5 to 40 o C It will operate in a relative humidity of...

Страница 6: ...BS5839 installations other cable types may be suitable Depending on the environment the cables may need mechanical protection such as a conduit 3 2 MAINS WIRING RECOMMENDATIONS The Mains supply to the...

Страница 7: ...ector will connect the ve to a 470R load resistor or a polarisation diode to enable the detector to work correctly with European Fire Alarm Panels For more specific device wiring information please re...

Страница 8: ...dition to a larger addressable fire alarm system 3 5 3 Fire Alarm Routing Equipment Output F A R E Monitored 24V nominal output This is a 24V 100mA output that activates in any fire condition and is u...

Страница 9: ...el box If a grommet is removed fill the hole with a brass cable gland If any knockout is removed but subsequently not used it should be covered up The 230Va c Mains cable must be fed into the enclosur...

Страница 10: ...to apply power to the panel before connecting any devices to check for correct operation and to familiarise yourself with the fire alarm panels controls 5 2 CONNECTING THE BATTERIES Figure 4 Battery...

Страница 11: ...to the appropriate connector block on the Termination PCB as shown in Figure 6 below For detailed detection and alarm circuit wiring diagrams please refer to pages 6 and 7 Figure 6 Detector and Sound...

Страница 12: ...TTING EXTERNAL SOUNDER DELAY IN MINUTES e g The above example would have a delay of 1 minute 0 No Delay 1 1 Minute 2 2 Minutes 3 3 Minutes 4 4 Minutes 5 5 Minutes 6 6 Minutes 7 7 Minutes 8 8 Minutes 9...

Страница 13: ...lit The item that has been disabled will now flash 3 quick flashes then on This means that it has been disabled but is still the focus of the disablement select de select operation If scroll is presse...

Страница 14: ...PROGRAMME ZONE IN TEST NOTE Only one zone can be programmed in test at any one time 1 Insert and turn control key to enabled position 2 Press FUNCTION button twice The General Zone test LED is now on...

Страница 15: ...ible with this FACP Note that some makes of detector will require a series resistor or diode to be fitted to work properly There is usually a spare connector on the base to accommodate this check inst...

Страница 16: ...fault The recommended setting it to monitor via the motherboard 10 5 SOUNDER FAULTS Check that the correct END of Line resistor has been fitted 10K brown black orange gold Check that all sounder fuse...

Страница 17: ...The required standby is 24 hours It will need to operate in alarm for hour Calculate the battery size required TALM 0 5 Hr IALM panel 0 205mA IALM 4x10 x 0 025 1 0A This typical bell current is 25 mA...

Страница 18: ...including test mode 6 FAULT RELAY NO CM NC Activates on fault 7 F A R E FIRE ALARM ROUTING EQUIPMENT 8 SND 1 Connect to sounder circuit 1 sirens bells 9 SND 2 Connect to sounder circuit 2 sirens bell...

Страница 19: ...Date 23 07 2012 FS5 Sounder circuit 2 400mA time delay 5 x 20mm glass FS6 AUX Supply 250mA time delay 5 x 20mm glass FS7 Sounder circuit 3 400mA time delay 5 x 20mm glass FS8 Sounder circuit 4 400mA t...

Страница 20: ...utput 6 B FUSE Fuse for the second 24V output 7 BATTERY Battery connection 2 x 12V SLA batteries wired in series 8 FACTORY ADJUST Charger adjust pot DO NOT ADJUST 9 THERM Battery charger temperature c...

Страница 21: ...IRCUIT Determined by momentatily reversing the zone voltage SOUNDER ALARM OUTPUTS 4 x 400mA 29V DC Nominal Min 18 9V DC Max 31 9V DC AUXILIARY FAULT OUTPUT 1 x RELAY SELV 1A MAX AUXILIARY FIRE OUTPUT...

Страница 22: ...a SA1 2EN 12 0359 CPD 0143 EN54 2 1997 A1 2002 A2 2006 EN54 4 1997 A1 2002 A2 2006 Control and indicating equipment for fire detection and fire alarm systems for buildings PMP8 PMP16 PMP24 Provided op...

Отзывы: