PREMIER M PLUS INSTALLATION MANUAL
Approved Document No: GLT.MAN-111
PAGE
10
Issue : 2.8 Author: NJ Date: 23/07/2012
6. FIELD DEVICE TERMINATION
6.1 TERMINATING THE DETECTION AND ALARM (SOUNDER) CIRCUITS.
All cables entering the enclosure should have cable glands fitted, and their earth screens connected to the Earth bar as shown. This
will ensure a good EMC performance. The Detection and Sounder circuits should be connected to the appropriate connector block
on the Termination PCB as shown in Figure 6 below.
(For detailed detection and alarm circuit wiring diagrams, please refer to pages 6 and 7)
Figure 6: Detector and Sounder Circuit Connection.
6.2 AUXILIARY INPUT AND OUTPUT TERMINATIONS
Connect auxiliary input and output cables to the appropriate connector block terminals on the Termination PCB (See Page 18).
Screened cables should be terminated at the earth bar, as per figure 6.
For a full description of the inputs and outputs available on the Premier M Plus range of Fire Panels, including typical wiring
diagrams please refer to page 8.