EXPro Installation Manual
Approved Document No: GLT-212-7-1
Page 4
Issue: 1.7 Author: MF/NRPJ Date: 05/07/2021
INTRODUCTION
THIS EXTINGUISING CONTROL PANEL IS CLASS 1 EQUIPMENT AND
MUST
BE EARTHED
This equipment must be installed and maintained by a qualified and technically competent
person.
HANDLING THE PCBS
If the PCBS are to be removed to ease fitting the enclosure and cables, care must be taken to avoid
damage by static.
The best method is to wear an earth strap, but touching any earth point (e.g. building plumbing) will
help to discharge any static. Hold PCBs by their sides, avoiding contact with any components. Always
handle PCBs by their sides and avoid touching the legs of any components. Keep the PCBs away from
damp and/or dirty areas, e.g. in a small cardboard box.
USING THIS MANUAL
This manual explains, in a step-by-step manner, the procedure for the installation of the EXPro
combined fire and extinguishing control panel.
ABOUT THE EXPRO
The Premier EXPRO is a 2 zone, 1 area extinguishing panel. It is designed to operate in Environmental
Class A (temperature range of - 5 °C to + 40 °C)
It has 2 zones dedicated to the extinguishing section. These are known as crossed or co-incidence
zones. Both circuits will need to be triggered in order to activate the extinguishing circuit. This kind
of operation also referred to as “double – knock”
The Extinguishing section is designed to BS EN 12094-1:2003.
The panel has an integral Manual Release switch fitted to the front of the panel.
The panel has monitored inputs for field connections, such as manual release, abort, etc.
The panel has relay outputs for first & second stage alarms, fault, gas fired, and EXT for extract fan.
The panel has an add-on board that provides relay outputs for Auto, Manual, and Abort
The Premier EXPRO can be in any of the following conditions:-
Quiescent condition – i.e. System Normal
Fault condition
Disabled condition
Test condition
Pre-activated condition
The Premier EXPRO will enter the pre-activated condition (first stage alarm) within 1 second
of a detector on one of the crossed zones signalling an alarm
Activated condition
www.acornfiresecurity.com