EXPro Installation Manual
Approved Document No: GLT-212-7-1
Page 29
Issue: 1.7 Author: MF/NRPJ Date: 05/07/2021
PANEL SPECIFICATION
ENCLOSURE SPECIFICATION
Description
Value
Enclosure Size (L x W x D mm)
310 x 369 x 113
Top Cable Entries
20
ELECTRICAL SPECIFICATIONS
Electrical Description
Minimum
Nominal
Maximum
Mains Voltage
-15%
230 / 115 VAC 50-60Hz
+10%
Battery Voltage
2 x 12V SLA
Battery Size
3.4Ah
7.2Ah
Power Supply Type
Non-Integral (Switch Mode)
PSU Output Voltage
17.0V
29.5V
31.5V
Imax A
21mA
Imax B
1.51A
Imin
14mA
Switching Frequency
100kHz
Output Voltage Ripple
700mV
Max current draw by PSE
2mA
Max Battery Internal
Resistance RiMAX
2.8 Ω
CIE DC Input Voltage
21.5V DC
29.5V DC
31.5V DC
Charger Voltage
27.6VDC @ 20°C
Charger Capacity
3.4Ah
7.2Ah
Battery Deep Discharge
Protection
Battery Shutdown at <20.3V
@ battery terminals
Number of Zones
2 Crossed Zones
Maximum devices per zone
32
1
st
Stage Sounder Alarm
Outputs
2x 150mA @ 19.8V
DC
2x 150mA @ 29.5V DC
2x 150mA @ 31.5V DC
2
nd
Stage Sounder Alarm
Outputs
1x 250mA @ 19.8V
DC
1x 250mA @ 29.5V DC
1x 250mA @ 31.5V DC
Bottle Output
1x 1A @ 19.8V DC
1x 1A @ 29.5V DC
1x 1A @ 31.5V DC
1
st
Stage Relay Output
1 x Volt Free Relay SELV,
1A Max
2
nd
Stage Relay Output
1 x Volt Free Relay SELV,
1A Max
Gas Fired Relay Output
1 x Volt Free Relay SELV,
1A Max
Ext Relay Output
1 x Volt Free Relay SELV,
1A Max
FUSE RATINGS
Fuse
Description
Rating
Battery
Battery Protection Fuse
2A fast blow, glass 250V
For continued protection, please ensure that any fuses that need to be replaced are replaced with
fuses of the correct rating.
www.acornfiresecurity.com