EXPro Installation Manual
Approved Document No: GLT-212-7-1
Page 16
Issue: 1.7 Author: MF/NRPJ Date: 05/07/2021
Use the
NEXT
and
PREV
button to cycle through items that can be disabled, pressing
OK
toggles the item between the enabled/disabled states:
Zone 1
Prevents the panel from responding to an alarm in zone 1
Zone 2
Prevents the panel from responding to an alarm in zone 2
Gas Fired input
Prevents the panel from responding to the gas fired signal
Manual release
Prevents the panel from responding to a manual release
Auto Manual
Prevents the external switching between auto and manual mode.
Switching between auto and manual mode can still be done from the
panel.
Abort Input
Disables the Abort input. The panel will not enter the alarm condition
if the abort input is disabled.
Low Pressure Input
Prevents the panel from responding to a low pressure signal.
Sounder 1A
Disables sounder 1A
Sounder 1B
Disables sounder 1B
Sounder 2
Disables the second stage sounder. The panel will not enter the
Activated condition if the second stage sounder is disabled.
Bottle Output
Disables the bottle output. The panel will not enter the Activated
condition if the bottle output is disabled.
External Fan
Disables the output to the external fan
When an item is disabled the GENERAL DISABLEMENT LED will light, along with the
corresponding FLT/TEST/DISABLED LED.
Press CANCEL to exit out of the disablement menu, the item will remain disabled until it is
manually re-enabled.
Test:
Allows the user/engineer to put an input or output into test mode.
Use the
NEXT
and
PREV
button to cycle through items that can be placed in test mode,
pressing
OK
puts the input into test mode.
When an input or output is in test mode the panel will indicate if it has been activated, but is
prevented from entering the normal sequence of events (such as activating sounders or
bottle output) associated with that input.
Note
: Only one input/output can be programmed in test mode at any one time.
*TEST MENU *
Low Pressure input
www.acornfiresecurity.com