EXPro Installation Manual
Approved Document No: GLT-212-7-1
Page 30
Issue: 1.7 Author: MF/NRPJ Date: 05/07/2021
DESIGN SPECIFICATIONS
The Premier EXPro is a combined extinguishing control panel & fire alarm control panel.
The Fire Alarm control Section has been designed in accordance with EN54-2:1998 A1 + A2 - Fire
Detection & Fire Alarm Systems – Control & Indicating Equipment
The Extinguishing control section has been designed in accordance with BSEN12094-1:2003 –
Fixed Fire fighting Systems – Components for Gas Extinguishing Systems – Requirements and
Test Methods for Electrical Automatic Control & Delay Devices
The Power Supply Section has been designed in accordance with EN54-4:1998 A1 + A2 - Fire
Detection & Fire Alarm Systems – Power Supply Equipment
FIRE ALARM CONTROL SECTION.
As well as meeting the requirements of EN54-2:1998 A1 + A2, the Premier EXPro also has the
following options with requirements:-
Clause 7.8 Output to fire alarm devices (Option with requirements)
Clause 10 Test Condition (Option with requirements)
EXTINGUISHING CONTROL S ECTION.
As well as meeting the requirements of BSEN12094-1:2003 the Premier EX Pro also has the
following options with requirements:-
Clause 4.17
Delay of extinguishing signal (Option with requirements)
Clause 4.18
Signal representing the flow of extinguishing agent (Option with
requirements)
Clause 4.21
Control of flooding time (Option with requirements)
Clause 4.23
Manual Only Mode (Option with requirements)
Clause 4.26
Triggering of equipment outside the system (Option with requirements)
Clause 4.27
Emergency Abort Device (Option with requirements)
Clause 4.30
Activation of alarm devices with different signals (Option with
requirements)
www.acornfiresecurity.com