MANUAL MODE  

In  this  mode  operation,  Zone  Fire  and  Fault  alarms  are  still  in  operation,  and  first  & second 
stage  sounders  will  operate,  but  the  bottle  output  to  the  extinguishing  agent will not operate.  
 

RESET  

To  reset  panel  from  a  first  stage  alarm  condition, activate the controls and  press  START/STOP 
SOUNDERS, followed by SILENCE BUZZER,  then RESET.  
 
If  the  panel  enters  the  second  stage  alarm  (while  in  automatic  mode),  the  panel cannot  be 
reset  until  the  bottle  output  has  operated,  and  the  reset  inhibit  timer  has ended.  
 
The  panel  can  NOT  be  reset  from  a  fault  condition.  All  faults  are  non  latching,  so when a 
fault clears from the panel it will be automatically cleared from the display.  
 
In  the  event  of  an  alarm  in  the  peripheral  fire  zones  &  crossed  extinguishing  zones 
simultaneously,  the reset button can be used to reset  the peripheral zones, but  won`t have an 
effect on the extinguishing zones until the reset inhibit timer has ended.  
 

FAULTS  

When a fault is detected the relevant LED will illuminate and the buzzer will sound. The LCD will 
display details of the fault(s) and show each detected fault in turn. Enable the controls and press the 
Silence Buzzer button to silence the panel. 
 
Press the NEXT and PREV buttons to manually cycle through the list of faults, the display will show 
the number of faults in the lower right corner. 
 
 

 

 

 

 

*** DEVICE FAULT *** 

 

BOTTLE OUTPUT O/C 

01/03

 

 

Содержание Premier EXPRO

Страница 1: ...EXPro User Manual Approved Document No GLT 212 7 2 Page 1 Issue 1 1 Author NRPJ Date 14 07 2014 USER MANUAL MAINTENANCE GUIDE LOG BOOK...

Страница 2: ...CONTROLS 8 PANEL MENUS 9 PANEL OPERATION 12 NORMAL OPERATION 12 FIRE ALARM CONDITION 12 WHAT TO DO IN THE EVENT OF A FIRE 12 RESETTING FROM AN ALARM CONDITION 12 MANUAL EVACUATION 13 FIRST STAGE ALARM...

Страница 3: ...ract fan The panel has an add on board that provides relay outputs for Auto Manual and Abort The Premier EXPRO can be in any of the following conditions Quiescent condition i e System Normal Fault con...

Страница 4: ...cluding start evacuation silence alarms silence faults and system reset 47 2 e 6 Take appropriate action to limit the rate of false alarms 47 2 f 7 Ensure that all detectors and manual call points rem...

Страница 5: ...t by authorised service personnel only Check every detector call point sounder and all auxiliary equipment for correct operation Check Cage output Voltage 29 5VDC Charger Voltage 27 6Vnormal Battery V...

Страница 6: ...n alarm condition Common Fault Yellow Indicates when the panel is in a fault condition General Disablement Yellow Indicates when an Input or Output has been disabled General Test Yellow Indicates when...

Страница 7: ...and 2nd stage zones are in alarm Pre Activated Red Indicates when there is a first stage alarm Manual Release Red Indicates when the Manual release switch has been activated Flooding Zone FLT Yellow I...

Страница 8: ...Stop 1st Stage Sounders Used to silence the 1st stage sounders Silence Buzzer Used to silence the internal buzzer in a fault or alarm condition Reset Used to reset the fire detection zone Reset CIE U...

Страница 9: ...ne This menu allows the user engineer to view the following information Logs The Log can store up to 249 events Use the NEXT and PREV buttons to scroll through the events Disable Allows the user engin...

Страница 10: ...abled Bottle Output Disables the bottle output The panel will not enter the Activated condition if the bottle output is disabled External Fan Disables the output to the external fan When an item is di...

Страница 11: ...EXPro User Manual Approved Document No GLT 212 7 2 Page 11 Issue 1 1 Author NRPJ Date 14 07 2014 Change Time Allows the user engineer to set the system clock SET UP TIME 12 00...

Страница 12: ...fire alarm panel 3 Investigate to determine the cause of the alarm Look for the detector in the zone in alarm that signalled the fire The detector that signalled an alarm will have its RED ALARM LED o...

Страница 13: ...ond Zone the second stage alarm is initiated The second stage sounder will be pulsed on for 1 second then off for 1 second This will be repeated as the timer counts down The two zone alarm LEDs will b...

Страница 14: ...e reset from a fault condition All faults are non latching so when a fault clears from the panel it will be automatically cleared from the display In the event of an alarm in the peripheral fire zones...

Страница 15: ...User Manual Approved Document No GLT 212 7 2 Page 15 Issue 1 1 Author NRPJ Date 14 07 2014 LOG BOOK MAINTENANCE WORK DATE TIME ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL WORK REQUIRED S...

Страница 16: ...212 7 2 Page 16 Issue 1 1 Author NRPJ Date 14 07 2014 UNWANTED ALARMS DATE TIME ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEDED YES NO MAINTENANCE FINDINGS CATEGORY OF...

Страница 17: ...Manual Approved Document No GLT 212 7 2 Page 17 Issue 1 1 Author NRPJ Date 14 07 2014 ALL OTHER EVENTS DATE TIME ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE IF KNOWN ACTION REQUIRED DATE COMPLETED...

Страница 18: ...fication History Do Not Print this Page when creating PDF Of the manual Issue Date Changes 1 0 First release of manual 1 1 14 10 2013 Corrected manual header Added maintenance info Corrected event log...

Отзывы: