EXPro User Manual 

 

 

Approved Document No: GLT-212-7-2 

 

Page 10 

Issue: 1.1   Author: NRPJ   Date: 14/07/2014 

 
Zone 1 

Prevents the panel from responding to an alarm in zone 1 

Zone 2 

Prevents the panel from responding to an alarm in zone 2 

Gas Fired input 

Prevents the panel from responding to the gas fired signal 

Manual release 

Prevents the panel from responding to a manual release 

Auto Manual 

Prevents the external switching between auto and manual mode. 
Switching between auto and manual mode can still be done from the 
panel. 

Abort Input 

Disables the Abort input. The panel will not enter the Activated 
condition if the abort input is disabled. 

Low Pressure Input 

Prevents the panel from responding to a low pressure signal. 

Sounder 1A 

Disables sounder 1A 

Sounder 1B 

Disables sounder 1B 

Sounder 2 

Disables the second stage sounder. The panel will not enter the 
Activated condition if the second stage sounder is disabled. 

Bottle Output 

Disables the bottle output. The panel will not enter the Activated 
condition if the bottle output is disabled 

External Fan 

Disables the output to the external fan 

 
When an item is disabled the GENERAL DISABLEMENT LED will light, along with the 

corresponding FLT/TEST/DISABLED LED. 

Press CANCEL to exit out of the disablement menu, the item will remain disabled until it is 

manually re-enabled. 

Test:

 Allows the user/engineer to put an input or output into test mode. 

 

 

Use the 

NEXT

 and 

PREV

 button to cycle through items that can be placed in test mode, 

pressing 

OK

 puts the input into test mode.  

 
When an input or output is in test mode the panel will indicate if it has been activated, but is 
prevented from entering the normal sequence of events (such as activating sounders or 
bottle output) associated with that input. 
 

Note

: Only one input/output can be programmed in test mode at any one time. 

 

 

 

The panel will automatically exit from a test condition after 15 minutes. The test condition 
can be manually exited from the test menu. 

*** Zone In Test *** 

 

Zone 1 

Time Left: 15:00 

 

*TEST MENU * 

 

Low Pressure input 

 

Содержание Premier EXPRO

Страница 1: ...EXPro User Manual Approved Document No GLT 212 7 2 Page 1 Issue 1 1 Author NRPJ Date 14 07 2014 USER MANUAL MAINTENANCE GUIDE LOG BOOK...

Страница 2: ...CONTROLS 8 PANEL MENUS 9 PANEL OPERATION 12 NORMAL OPERATION 12 FIRE ALARM CONDITION 12 WHAT TO DO IN THE EVENT OF A FIRE 12 RESETTING FROM AN ALARM CONDITION 12 MANUAL EVACUATION 13 FIRST STAGE ALARM...

Страница 3: ...ract fan The panel has an add on board that provides relay outputs for Auto Manual and Abort The Premier EXPRO can be in any of the following conditions Quiescent condition i e System Normal Fault con...

Страница 4: ...cluding start evacuation silence alarms silence faults and system reset 47 2 e 6 Take appropriate action to limit the rate of false alarms 47 2 f 7 Ensure that all detectors and manual call points rem...

Страница 5: ...t by authorised service personnel only Check every detector call point sounder and all auxiliary equipment for correct operation Check Cage output Voltage 29 5VDC Charger Voltage 27 6Vnormal Battery V...

Страница 6: ...n alarm condition Common Fault Yellow Indicates when the panel is in a fault condition General Disablement Yellow Indicates when an Input or Output has been disabled General Test Yellow Indicates when...

Страница 7: ...and 2nd stage zones are in alarm Pre Activated Red Indicates when there is a first stage alarm Manual Release Red Indicates when the Manual release switch has been activated Flooding Zone FLT Yellow I...

Страница 8: ...Stop 1st Stage Sounders Used to silence the 1st stage sounders Silence Buzzer Used to silence the internal buzzer in a fault or alarm condition Reset Used to reset the fire detection zone Reset CIE U...

Страница 9: ...ne This menu allows the user engineer to view the following information Logs The Log can store up to 249 events Use the NEXT and PREV buttons to scroll through the events Disable Allows the user engin...

Страница 10: ...abled Bottle Output Disables the bottle output The panel will not enter the Activated condition if the bottle output is disabled External Fan Disables the output to the external fan When an item is di...

Страница 11: ...EXPro User Manual Approved Document No GLT 212 7 2 Page 11 Issue 1 1 Author NRPJ Date 14 07 2014 Change Time Allows the user engineer to set the system clock SET UP TIME 12 00...

Страница 12: ...fire alarm panel 3 Investigate to determine the cause of the alarm Look for the detector in the zone in alarm that signalled the fire The detector that signalled an alarm will have its RED ALARM LED o...

Страница 13: ...ond Zone the second stage alarm is initiated The second stage sounder will be pulsed on for 1 second then off for 1 second This will be repeated as the timer counts down The two zone alarm LEDs will b...

Страница 14: ...e reset from a fault condition All faults are non latching so when a fault clears from the panel it will be automatically cleared from the display In the event of an alarm in the peripheral fire zones...

Страница 15: ...User Manual Approved Document No GLT 212 7 2 Page 15 Issue 1 1 Author NRPJ Date 14 07 2014 LOG BOOK MAINTENANCE WORK DATE TIME ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL WORK REQUIRED S...

Страница 16: ...212 7 2 Page 16 Issue 1 1 Author NRPJ Date 14 07 2014 UNWANTED ALARMS DATE TIME ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEDED YES NO MAINTENANCE FINDINGS CATEGORY OF...

Страница 17: ...Manual Approved Document No GLT 212 7 2 Page 17 Issue 1 1 Author NRPJ Date 14 07 2014 ALL OTHER EVENTS DATE TIME ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE IF KNOWN ACTION REQUIRED DATE COMPLETED...

Страница 18: ...fication History Do Not Print this Page when creating PDF Of the manual Issue Date Changes 1 0 First release of manual 1 1 14 10 2013 Corrected manual header Added maintenance info Corrected event log...

Отзывы: