EXPro User Manual 

 

 

Approved Document No: GLT-212-7-2 

 

Page 12 

Issue: 1.1   Author: NRPJ   Date: 14/07/2014 

PANEL OPERATION  

NORMAL OPERATION  

With  the  controls inactive, under  normal  conditions  the system will be silent and the green 

“POWER LED” illuminated. The LCD will display “SYSTEM NORMAL” 

The  system  may  either be  in  “Automatic” or “Manual” mode of operation.  This will be evident 

by  the  illumination  of  either  the  “Automatic”  or  Manual”  LED.  In  Manual Mode,  the  bottle 

output  will  not  be activated  automatically.  It  must  be  started manually by pressing a 

manual release call point.  

FIRE ALARM CONDITION 

The Premier EXPro signals an alarm by the following:-  

 

Turn on the General Fire LED  

 

Turn on the Zonal Fire Indicator  

 

Turn on internal buzzer  

 

Start any sounders connected to the panels sounder circuits   

 

Activate the First Stage (fire) relay. (Note that the first stage repeater output will not 
activate. This only operates on an alarm from one of the crossed zones)  

 

WHAT TO DO IN THE EVENT OF A FIRE.  

1.

 

Follow the building evacuation procedure, and check that everyone has left the building 
safely.  

2.

 

The building fire officer or suitably trained responsible person should CAREFULLY enter 
the building, and locate the area of the alarm from the fire alarm  panel.  

3.

 

Investigate to determine the cause of the alarm. Look for the detector in the zone in 
alarm that signalled the fire. The detector that signalled an alarm will have its RED ALARM 
LED on.  

4.

 

If a small fire is found, a suitably trained person could tackle this with a suitable  fire 
extinguisher.  

5.

 

If a larger fire is found, leave the building immediately, and contact the fire brigade.  

6.

 

If no fire is found, make a note of the detector that signalled fire, and look for anything 
nearby that could be the cause of the activation, eg cooking, or use of a hot air gun etc.  

7.

 

Record findings in the fire alarm log book.  

 

RESETTING FROM AN ALARM CONDITION  

After the relevant action has been taken, the Premier EXPro fire alarm panel can be reset by the 

following:-  

1.

 

Gain user access to the panel by entering the password (default 2222) 

2.

 

Press Start/Stop 1

st

 Stage Sounder button, this will silence the external sounders.  

3.

 

Press  Silence  Buzzer  button. This will silence the panel`s internal buzzer.  

4.

 

Press the Reset button. This will return the panel to its normal condition. If the panel goes 
straight back into alarm, then the cause of the alarm has not been  cleared. This could be a 
detector still exposed to smoke, or a call point still in the active position. Investigate for a 
call point, or detector that still has its RED ALARM LED on. Reset the call point, or clear the 
smoke. If the problem persists, contact an engineer.  

Содержание Premier EXPRO

Страница 1: ...EXPro User Manual Approved Document No GLT 212 7 2 Page 1 Issue 1 1 Author NRPJ Date 14 07 2014 USER MANUAL MAINTENANCE GUIDE LOG BOOK...

Страница 2: ...CONTROLS 8 PANEL MENUS 9 PANEL OPERATION 12 NORMAL OPERATION 12 FIRE ALARM CONDITION 12 WHAT TO DO IN THE EVENT OF A FIRE 12 RESETTING FROM AN ALARM CONDITION 12 MANUAL EVACUATION 13 FIRST STAGE ALARM...

Страница 3: ...ract fan The panel has an add on board that provides relay outputs for Auto Manual and Abort The Premier EXPRO can be in any of the following conditions Quiescent condition i e System Normal Fault con...

Страница 4: ...cluding start evacuation silence alarms silence faults and system reset 47 2 e 6 Take appropriate action to limit the rate of false alarms 47 2 f 7 Ensure that all detectors and manual call points rem...

Страница 5: ...t by authorised service personnel only Check every detector call point sounder and all auxiliary equipment for correct operation Check Cage output Voltage 29 5VDC Charger Voltage 27 6Vnormal Battery V...

Страница 6: ...n alarm condition Common Fault Yellow Indicates when the panel is in a fault condition General Disablement Yellow Indicates when an Input or Output has been disabled General Test Yellow Indicates when...

Страница 7: ...and 2nd stage zones are in alarm Pre Activated Red Indicates when there is a first stage alarm Manual Release Red Indicates when the Manual release switch has been activated Flooding Zone FLT Yellow I...

Страница 8: ...Stop 1st Stage Sounders Used to silence the 1st stage sounders Silence Buzzer Used to silence the internal buzzer in a fault or alarm condition Reset Used to reset the fire detection zone Reset CIE U...

Страница 9: ...ne This menu allows the user engineer to view the following information Logs The Log can store up to 249 events Use the NEXT and PREV buttons to scroll through the events Disable Allows the user engin...

Страница 10: ...abled Bottle Output Disables the bottle output The panel will not enter the Activated condition if the bottle output is disabled External Fan Disables the output to the external fan When an item is di...

Страница 11: ...EXPro User Manual Approved Document No GLT 212 7 2 Page 11 Issue 1 1 Author NRPJ Date 14 07 2014 Change Time Allows the user engineer to set the system clock SET UP TIME 12 00...

Страница 12: ...fire alarm panel 3 Investigate to determine the cause of the alarm Look for the detector in the zone in alarm that signalled the fire The detector that signalled an alarm will have its RED ALARM LED o...

Страница 13: ...ond Zone the second stage alarm is initiated The second stage sounder will be pulsed on for 1 second then off for 1 second This will be repeated as the timer counts down The two zone alarm LEDs will b...

Страница 14: ...e reset from a fault condition All faults are non latching so when a fault clears from the panel it will be automatically cleared from the display In the event of an alarm in the peripheral fire zones...

Страница 15: ...User Manual Approved Document No GLT 212 7 2 Page 15 Issue 1 1 Author NRPJ Date 14 07 2014 LOG BOOK MAINTENANCE WORK DATE TIME ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL WORK REQUIRED S...

Страница 16: ...212 7 2 Page 16 Issue 1 1 Author NRPJ Date 14 07 2014 UNWANTED ALARMS DATE TIME ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEDED YES NO MAINTENANCE FINDINGS CATEGORY OF...

Страница 17: ...Manual Approved Document No GLT 212 7 2 Page 17 Issue 1 1 Author NRPJ Date 14 07 2014 ALL OTHER EVENTS DATE TIME ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE IF KNOWN ACTION REQUIRED DATE COMPLETED...

Страница 18: ...fication History Do Not Print this Page when creating PDF Of the manual Issue Date Changes 1 0 First release of manual 1 1 14 10 2013 Corrected manual header Added maintenance info Corrected event log...

Отзывы: