background image

EXPro User Manual 

 

 

Approved Document No: GLT-212-7-2 

 

Page 17 

Issue: 1.1   Author: NRPJ   Date: 14/07/2014 

ALL OTHER EVENTS 

DATE 

TIME 

ZONE/ 
LOCATION 

DETAILS OF EVENT (INCLUDING 
CAUSE IF KNOWN) 

ACTION REQUIRED 

DATE 
COMPLETED 

INITIALS 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Содержание Premier EXPRO

Страница 1: ...EXPro User Manual Approved Document No GLT 212 7 2 Page 1 Issue 1 1 Author NRPJ Date 14 07 2014 USER MANUAL MAINTENANCE GUIDE LOG BOOK...

Страница 2: ...CONTROLS 8 PANEL MENUS 9 PANEL OPERATION 12 NORMAL OPERATION 12 FIRE ALARM CONDITION 12 WHAT TO DO IN THE EVENT OF A FIRE 12 RESETTING FROM AN ALARM CONDITION 12 MANUAL EVACUATION 13 FIRST STAGE ALARM...

Страница 3: ...ract fan The panel has an add on board that provides relay outputs for Auto Manual and Abort The Premier EXPRO can be in any of the following conditions Quiescent condition i e System Normal Fault con...

Страница 4: ...cluding start evacuation silence alarms silence faults and system reset 47 2 e 6 Take appropriate action to limit the rate of false alarms 47 2 f 7 Ensure that all detectors and manual call points rem...

Страница 5: ...t by authorised service personnel only Check every detector call point sounder and all auxiliary equipment for correct operation Check Cage output Voltage 29 5VDC Charger Voltage 27 6Vnormal Battery V...

Страница 6: ...n alarm condition Common Fault Yellow Indicates when the panel is in a fault condition General Disablement Yellow Indicates when an Input or Output has been disabled General Test Yellow Indicates when...

Страница 7: ...and 2nd stage zones are in alarm Pre Activated Red Indicates when there is a first stage alarm Manual Release Red Indicates when the Manual release switch has been activated Flooding Zone FLT Yellow I...

Страница 8: ...Stop 1st Stage Sounders Used to silence the 1st stage sounders Silence Buzzer Used to silence the internal buzzer in a fault or alarm condition Reset Used to reset the fire detection zone Reset CIE U...

Страница 9: ...ne This menu allows the user engineer to view the following information Logs The Log can store up to 249 events Use the NEXT and PREV buttons to scroll through the events Disable Allows the user engin...

Страница 10: ...abled Bottle Output Disables the bottle output The panel will not enter the Activated condition if the bottle output is disabled External Fan Disables the output to the external fan When an item is di...

Страница 11: ...EXPro User Manual Approved Document No GLT 212 7 2 Page 11 Issue 1 1 Author NRPJ Date 14 07 2014 Change Time Allows the user engineer to set the system clock SET UP TIME 12 00...

Страница 12: ...fire alarm panel 3 Investigate to determine the cause of the alarm Look for the detector in the zone in alarm that signalled the fire The detector that signalled an alarm will have its RED ALARM LED o...

Страница 13: ...ond Zone the second stage alarm is initiated The second stage sounder will be pulsed on for 1 second then off for 1 second This will be repeated as the timer counts down The two zone alarm LEDs will b...

Страница 14: ...e reset from a fault condition All faults are non latching so when a fault clears from the panel it will be automatically cleared from the display In the event of an alarm in the peripheral fire zones...

Страница 15: ...User Manual Approved Document No GLT 212 7 2 Page 15 Issue 1 1 Author NRPJ Date 14 07 2014 LOG BOOK MAINTENANCE WORK DATE TIME ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL WORK REQUIRED S...

Страница 16: ...212 7 2 Page 16 Issue 1 1 Author NRPJ Date 14 07 2014 UNWANTED ALARMS DATE TIME ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEDED YES NO MAINTENANCE FINDINGS CATEGORY OF...

Страница 17: ...Manual Approved Document No GLT 212 7 2 Page 17 Issue 1 1 Author NRPJ Date 14 07 2014 ALL OTHER EVENTS DATE TIME ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE IF KNOWN ACTION REQUIRED DATE COMPLETED...

Страница 18: ...fication History Do Not Print this Page when creating PDF Of the manual Issue Date Changes 1 0 First release of manual 1 1 14 10 2013 Corrected manual header Added maintenance info Corrected event log...

Отзывы: