ZoningBOX 6/ ZoningBOX 4
Technical Support:
42
1=Heat
3=Cool
9=Fan
14=Dry
92, 125
1 Bit
I
C - W T U
DPT_Ack
0/1
[Unit x] Heat Mode
0 = Ignored; 1 = Activate Heat Mode
93, 126
1 Bit
O
C R - T -
DPT_Switch
0/1
[Unit x] Heat Mode (Status)
0 = Off; 1 = On
94, 127
1 Bit
I
C - W T U
DPT_Ack
0/1
[Unit x] Cool Mode
0 = Ignored; 1 = Activate Cool Mode
95, 128
1 Bit
O
C R - T -
DPT_Switch
0/1
[Unit x] Cool Mode (Status)
0 = Off; 1 = On
96, 129
1 Bit
I
C - W T U
DPT_Ack
0/1
[Unit x] Fan Mode
0 = Ignored; 1 = Activate Fan Mode
97, 130
1 Bit
O
C R - T -
DPT_Switch
0/1
[Unit x] Fan Mode (Status)
0 = Off; 1 = On
98, 131
1 Bit
I
C - W T U
DPT_Ack
0/1
[Unit x] Dry Mode
0 = Ignored; 1 = Activate Dry Mode
99, 132
1 Bit
O
C R - T -
DPT_Switch
0/1
[Unit x] Dry Mode (Status)
0 = Off; 1 = On
100, 133
1 Bit
I
C - W T U
DPT_Heat_Cool
0/1
[Unit x] Simplified Mode
0 = Cool; 1 = Heat
101, 134
1 Bit
O
C R - T -
DPT_Heat_Cool
0/1
[Unit x] Simplified Mode (Status)
0 = Cool; 1 = Heat
102, 135
2 Bytes
O
C R - T -
DPT_Value_Temp
-273.00º -
670433.28º
[Unit x] Global Temperature Setpoint
Setpoint to HVAC Unit
103, 136
1 Bit
I
C - W T U
DPT_Enable
0/1
[Unit x] Setpoint Limits
0 = Disabled; 1 = Enabled
104, 137
2 Bytes
I
C - W T U
DPT_Value_Temp
-273.00º -
670433.28º
[Unit x] Minimum (Cool Mode)
Minimum in Range
105, 138
2 Bytes
I
C - W T U
DPT_Value_Temp
-273.00º -
670433.28º
[Unit x] Maximum (Heat Mode)
Maximum in Range
106, 139
2 Bytes
I
C - W T U
DPT_Value_Temp
-273.00º -
670433.28º
[Unit x] Return Temperature
Return Temp. from External Sensor
107, 140
1 Byte
I
C - W T U
DPT_Scaling
0% - 100%
[Unit x] Fan: Percentage Control
Min = 1 - 50%; Max = 51 - 100%
1 Byte
I
C - W T U
DPT_Scaling
0% - 100%
[Unit x] Fan: Percentage Control
Min = 1 - 33%; Med = 34 - 67%; Max = 68 -
100%
108, 141
1 Byte
O
C R - T -
DPT_Scaling
0% - 100%
[Unit x] Fan: Speed Percentage (Status)
Min = 33%; Med = 67%; Max = 100%
1 Byte
O
C R - T -
DPT_Scaling
0% - 100%
[Unit x] Fan: Speed Percentage (Status)
Min = 50%; Max = 100%
109, 142
1 Bit
I
C - W T U
DPT_Step
0/1
[Unit x] Fan: Step Control
0 = Decrease; 1 = Increase
110, 143
1 Byte
I
C - W T U
DPT_Fan_Stage
0 - 255
[Unit x] Fan: Enumeration Control
1 = Min.; 2 = Max.
1 Byte
I
C - W T U
DPT_Fan_Stage
0 - 255
[Unit x] Fan: Enumeration Control
1 = Min.; 2 = Med.; 3 = Max.
111, 144
1 Byte
O
C R - T -
DPT_Fan_Stage
0 - 255
[Unit x] Fan: Speed Enumeration (Status)
1 = Min.; 2 = Med.; 3 = Max.
1 Byte
O
C R - T -
DPT_Fan_Stage
0 - 255
[Unit x] Fan: Speed Enumeration (Status)
1 = Min.; 2 = Max.
112, 145
1 Bit
I
C - W T U
DPT_Ack
0/1
[Unit x] Fan: Speed Minimum
0 = Ignored; 1 = On
113, 146
1 Bit
I
C - W T U
DPT_Ack
0/1
[Unit x] Fan: Speed Intermediate
0 = Ignored; 1 = On
114, 147
1 Bit
I
C - W T U
DPT_Ack
0/1
[Unit x] Fan: Speed Maximum
0 = Ignored; 1 = On
115, 148
1 Bit
O
C R - T -
DPT_Switch
0/1
[Unit x] Fan: Speed Minimum (Status)
0 = Off; 1 = On
116, 149
1 Bit
O
C R - T -
DPT_Switch
0/1
[Unit x] Fan: Speed Intermediate (Status)
0 = Off; 1 = On