ZoningBOX 6 / ZoningBOX 4
Technical Support:
35
Power supply failure
: this is reported in case the input voltage differs from
230 VAC. In such case, grille operation is immediately interrupted.
Overheating
:
this is
reported in the unlikely event that ZoningBOX detectes
an internal temperature of 75º C or more. In such case, all grilles will remain
stopped until it lowers back to 65º C or less.
Note that the first three errors are reported per grille (one object is provided per
enabled grille), while the latter two are not (a sole object is provided for each error, with
independence of the number of grilles).
In addition, Zoning always informs about errors via the available LEDs on each output,
if any of the following errors have occurred: power supply failure, connection error
(short-circuit and open circuit error), overload error.
ERROR
LEDS DESCRIPTION
VISUAL NOTIFICATION
ZoningBOX 4
VISUAL NOTIFICATION
ZoningBOX 6
Power Supply
LED of each output blinks
(during 1 second) sequentially.
OUTPUTS
O1 O2 O3 O4
TIM
E (
s)
0
0,5
1
1,5
2
2,5
3
OUTPUTS
O1 O2 O3 O4 O5 O6
TIM
E (
s)
0
0,5
1
1,5
2
2,5
3
Connection
LED of the output affected by a
short circuit or open circuit
blinks every second.
OUTPUTS
O1 O2 O3 O4
TIM
E (
s)
0
0,5
1
1,5
2
2,5
3
OUTPUTS
O1 O2 O3 O4 O5 O6
TIM
E (
s)
0
0,5
1
1,5
2
2,5
3
Overload
Two blinks of 0.5 seconds
and 2 seconds rest on the
LED of the affected output.
OUTPUTS
O1 O2 O3 O4
TIM
E (
s)
0
0,5
1
1,5
2
2,5
3
OUTPUTS
O1 O2 O3 O4 O5 O6
TIM
E (
s)
0
0,5
1
1,5
2
2,5
3
Table 6.
Visual notification in case of error detection.