ZoningBOX 6 / ZoningBOX 4
Technical Support:
18
Joint mode (one byte)
: a 1-Byte object is provided together with the
corresponding status object, coded according to the following table.
Mode
KNX Value
Heating
1
Cooling
3
Fan
9
Dry Air
14
Table 1
Modes
Simplified mode (one bit)
:
a one-bit object is provided to allow simple
changeovers between Cooling (value “0”) and Heating (value “1”). In case the
Fan and Dry modes are activated through the above controls, the status
object of this one will show
the value “0”.
Every time a mode switchover takes place, all the enabled status objects will be sent,
no matter if the HVAC unit is on or off.
By default, the HVAC unit is assumed to be in the Cooling mode.
ETS PARAMETERISATION
The Mode configuration screen allows enabling the different mode control objects
available.
Figure 16.
Zoning - Mode
Joint Mode: enables the
“[Unit x] Mode” and “[Unit x] Mode (Status)” 1-Byte
objects.