parameterised NTP server and time zone. This functionality is only available in
Z41 Pro and Z41 COM. See section 3.2.14.
Time/Date Sending Period
: when enabled (value different from zero), whenever
the device is restarted, the date and time objects (
“
[General] Date
and
“
[General] Time
”) will be sent to the bus, and thereafter, they will be sent again
every time the period expires. Setting a new time to the device either through
object or from the date/time configuration window will not restart the count of the
sending period. Range: [0-65535] x 1 min. The default value is 10 min.
Note
:
to prevent time lags, it is advisable to only have one master clock within
the installation. Having multiple devices overwriting each other their time and date
registers periodically may end up inducing delays.
Thermostat n
: checkbox (unselected by default) that activates/deactivates the
Thermostat n parameter screen. See section 3.8.
Inputs
(only in Z41 Pro and Z41 Lite): checkbox (disabled by default) to
show/hide the additional Inputs screen. See section 3.9.
Heartbeat
(only in Z41 COM): checkbox (disabled by default) to incorporate a
one-
bit object to the project (“
[Heartbeat] Ob
ject to Send ‘1’
”) that will be sent
periodically with value “1” to notify that the device is still working (
still alive
).
Figura 37
Heartbeat
Note: the first sending after download or bus failure takes place with a delay of
up to 255 seconds, to prevent bus overload. The following sendings march the
period set.