Z41 Pro / Lite / COM
http://www.zennio.com
Tecnical Support:
http://support.zennio.com
118
Label for “Time OFF”
: permits customising the label shown next to the checkbox
that enables/disables the sending of the switch-off order. The default value is
“Time OFF”.
Label for “Scene”
: permits customising the label shown next to the checkbox
that enables/disables the scene sending. The default value is “Scene”.
Enablement
: sets the value to enable and disable the timer through the object
[Pn][Bi] Daily Timer Enabling
. The options are “0=Disable; 1=Enable” (default
option) “0=Enable; 1=Disable”.
Note
: the execution of user-defined timers is triggered on the detection of state
transitions, even if the clock does not specifically pass through the specified time.
In other words,
supposing one timed sending of the value “ON” at 10:00h am and
one timed sending of the value “OFF” at 8:00h pm, if the internal clock is set to
9:00h pm just after 10:00h am (and therefo
re after having sent the value “ON”),
then the “OFF” order corresponding to 8:00h pm will take place immediately after
the time change.
3.6.2.5.6
Chrono-thermostat
Boxes configured as chrono-thermostats let the final user schedule the timed sending of
temperature setpoint
orders
(preceded by switch-on orders) or
switch- off orders
to
a thermostat through the KNX bus.
To that end, it is necessary to configure the following two parameters:
Figure 117
Chrono-thermostat
Minimum Setpoint Value
: minimum setpoint value the user will be able to set.
Range: [-20, 95] x 1ºC. Default value: 18ºC.