MINiBOX 0-10V X3/X2/X1
Technical Support:
17
ETS PARAMETERISATION
The
Manual Control
(enable by default as explained in section 2.1) is configured from
the
“Configuration” sub tab itself under “Manual Control”.
Figure 6.
Manual control.
Manual Control
[
Disabled / Only Test Off Mode / Only Test On Mode /
Test
Off Mode + Test On Mode
]: Depending on the selection, the device will permit
using the manual control under the Test Off, the Test On, or both modes. Note
that, as stated before, using the Test Off mode does not require any special
action, while switching to Test On mode does require long-pressing the
Prog./Test button.
Lock Manual Control
[
disabled
/enabled
]: unless the above parameter has
been “Disabled”, the Lock Manual Control parameter provides an optional
procedure for locking the manual control in runtime. When this checkbox is
enabled, object “
Manual Control Lock
” turns visible, as well as two more
parameters:
➢
Value
[
0 = Lock; 1 = Unlock /
0 = Unlock; 1 = Lock
]: defines whether the
manual control lock/unlock should take place upon the reception of values
“0” and “1” respectively, or the opposite.
➢
Initialization
[
Unlocked / Locked /
Last Value
]: sets how the lock manual
control should be after the device start-up (after an ETS download or a
bus power failure). The option
“Last Value” will correspond to Unlocked
on the first start-up.