When the button is pressed, the device will act over the output according to the
duration of the button press and to the current output state:
➢
Short press:
action equivalent to a 0% or 100% control command in the
output control object. The status is sent via the associated status object.
➢
Long press:
initiates an increasing regulation if the output actual status
is 0%, or a decreasing regulation if it is 100%. For values between 0 and
100%, the regulation direction is switched with each long press. The
status object will be sent to the bus after stopping the press or reaching
the minimum or maximum value.
In Test Off mode, any press on the buttons of the
outputs disabled
by parameter will
have
no effect
.
Test On Mode
After entering the Test On mode, it will only be possible to control the outputs through
the on-board pushbuttons. Orders received through communication objects will be
ignored, regardless of the channel or the output they are addressed to.
Individual output
: the action performed on the output by pressing the physical
buttons will be the same as described in the Test Off mode except that the
status objects will not be affected.
Note
:
unlike in test off mode, in test on mode any type of output can be
controlled, not only the generic ones
.
Under the Test On mode, short and long presses will cause the
same effect for disabled
outputs
as for analog voltage outputs.
As described previously if the device is in Test On mode, any command sent from the
KNX bus to the actuator will not affect the outputs and no status objects will be sent (only
periodically timed objects such as Heartbeat or logic functions will continue to be sent to
the bus) while Test ON mode is active.
Important
:
the device is factory delivered with all the output channels configured as
disabled outputs, and with both manual modes (Test Off and Test On) enabled
.