MAXinBOX FC 0-10V FAN
http://www.zennio.com
Technical Support:
http://support.zennio.com
32
32
ETS PARAMETERISATION
Once the Master Light function has been enabled, a specific tab will be included in the
menu on the left. This new parameter screen () contains the following options:
Number of State Objects
: defines the number of 1-bit status objects
required. The minimum (and default) value is “1”, and the maximum is “12”.
These obj
ects are called “
[ML] Status Object n
”.
In addition, the general status object (“
[ML] General status
”) will always be
available in the project topology. It will be sent to the bus with a value of “1”
whenever there is at least one of the above state objects with such value.
Otherwise (i.e., if none of them has a value of “1”), it will be sent with a value
of “0”.
Trigger Value
: sets the value (“0”, “1” or “0/1”, being the latter the default
option) that will trigger, when received through “
[ML] Trigger
”, the master
action (the general switch-off or the courtesy switch-on).
General Switch-Off
.
➢
Delay
: defines a certain delay (once the trigger has been received)
before the execution of the general switch-off. The allowed range is 0 to
255 seconds.
➢
Binary Value
:
if checked, object “
[ML] General Switch-off: Binary
Object
” will be enabled, which will send one “0” whenever the general
switch-off takes off.
➢
Scaling
: if checked, object “
[ML] General Switch-off: Scaling
” will be
enabled, which will send a percentage v
alue (configurable in “
Value
”)
whenever the general switch-off takes off.
➢
Scene
: if checked, object “
[ML] General Switch-off: Scene
” will be
enabled, which will send a scene run / save order (configurable in
“
Action
” and “
Scene Number
”) whenever the general switch-off takes
off
➢
HVAC
: if checked, object “
[ML] General Switch-off: HVAC mode
” will
be enabled, which will send an HVAC thermostat mode value