ALLinBOX 1612 v2 / 88 / 46 / Hospitality
Technical Support:
50
2=Standby
3=Economy
4=Building
Protection
1475, 1513, 1551, 1589
2 Bytes
I
C - W - -
DPT_Value_Temp
-273.00º - 670433.28º
[Tx] Setpoint
Thermostat Setpoint Input
2 Bytes
I
C - W - -
DPT_Value_Temp
-273.00º - 670433.28º
[Tx] Basic Setpoint
Reference Setpoint
1476, 1514, 1552, 1590
1 Bit
I
C - W - -
DPT_Step
0/1
[Tx] Setpoint Step
0 = Decrease Setpoint; 1 =
Increase Setpoint
1477, 1515, 1553, 1591
2 Bytes
I
C - W - -
DPT_Value_Tempd
-671088.64º - 670433.28º
[Tx] Setpoint Offset
Float Offset Value
1478, 1516, 1554, 1592
2 Bytes
O
C R - T -
DPT_Value_Temp
-273.00º - 670433.28º
[Tx] Setpoint Status
Current Setpoint
1479, 1517, 1555, 1593
2 Bytes
O
C R - T -
DPT_Value_Temp
-273.00º - 670433.28º
[Tx] Basic Setpoint Status
Current Basic Setpoint
1480, 1518, 1556, 1594
2 Bytes
O
C R - T -
DPT_Value_Tempd
-671088.64º - 670433.28º
[Tx] Setpoint Offset Status
Current Setpoint Offset
1481, 1519, 1557, 1595
1 Bit
I
C - W - -
DPT_Reset
0/1
[Tx] Setpoint Reset
Reset Setpoint to Default
1 Bit
I
C - W - -
DPT_Reset
0/1
[Tx] Offset Reset
Reset Offset
1482, 1520, 1558, 1596
1 Bit
I
C - W - -
DPT_Heat_Cool
0/1
[Tx] Mode
0 = Cool; 1 = Heat
1483, 1521, 1559, 1597
1 Bit
O
C R - T -
DPT_Heat_Cool
0/1
[Tx] Mode Status
0 = Cool; 1 = Heat
1484, 1522, 1560, 1598
1 Bit
I
C - W - -
DPT_Switch
0/1
[Tx] On/Off
0 = Off; 1 = On
1485, 1523, 1561, 1599
1 Bit
O
C R - T -
DPT_Switch
0/1
[Tx] On/Off Status
0 = Off; 1 = On
1486, 1524, 1562, 1600
1 Bit
I/O
C R W - -
DPT_Switch
0/1
[Tx] Main System (Cool)
0 = System 1; 1 = System 2
1487, 1525, 1563, 1601
1 Bit
I/O
C R W - -
DPT_Switch
0/1
[Tx] Main System (Heat)
0 = System 1; 1 = System 2
1488, 1526, 1564, 1602
1 Bit
I
C - W - -
DPT_Enable
0/1
[Tx] Enable/Disable Secondary
System (Cool)
0 = Disable; 1 = Enable
1489, 1527, 1565, 1603
1 Bit
I
C - W - -
DPT_Enable
0/1
[Tx] Enable/Disable Secondary
System (Heat)
0 = Disable; 1 = Enable
1490, 1496, 1528, 1534,
1566, 1572, 1604, 1610
1 Byte
O
C R - T -
DPT_Scaling
0% - 100%
[Tx] [Sx] Control Variable (Cool)
PI Control (Continuous)
1491, 1497, 1529, 1535,
1567, 1573, 1605, 1611
1 Byte
O
C R - T -
DPT_Scaling
0% - 100%
[Tx] [Sx] Control Variable (Heat)
PI Control (Continuous)
1 Byte
O
C R - T -
DPT_Scaling
0% - 100%
[Tx] [Sx] Control Variable
PI Control (Continuous)
1492, 1498, 1530, 1536,
1568, 1574, 1606, 1612
1 Bit
O
C R - T -
DPT_Switch
0/1
[Tx] [Sx] Control Variable (Cool)
2-Point Control
1 Bit
O
C R - T -
DPT_Switch
0/1
[Tx] [Sx] Control Variable (Cool)
PI Control (PWM)
1493, 1499, 1531, 1537,
1569, 1575, 1607, 1613
1 Bit
O
C R - T -
DPT_Switch
0/1
[Tx] [Sx] Control Variable (Heat)
2-Point Control
1 Bit
O
C R - T -
DPT_Switch
0/1
[Tx] [Sx] Control Variable (Heat)
PI Control (PWM)
1 Bit
O
C R - T -
DPT_Switch
0/1
[Tx] [Sx] Control Variable
2-Point Control
1 Bit
O
C R - T -
DPT_Switch
0/1
[Tx] [Sx] Control Variable
PI Control (PWM)
1494, 1500, 1532, 1538,
1570, 1576, 1608, 1614
1 Bit
O
C R - T -
DPT_Switch
0/1
[Tx] [Sx] PI State (Cool)
0 = PI Signal 0%; 1 = PI Signal
Greater than 0%
1495, 1501, 1533, 1539,
1571, 1577, 1609, 1615
1 Bit
O
C R - T -
DPT_Switch
0/1
[Tx] [Sx] PI State (Heat)
0 = PI Signal 0%; 1 = PI Signal
Greater than 0%