ANNEX I. COMMUNICATION OBJECTS
“Functional range
” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a
particular meaning because of the specifications or restrictions from both the KNX standard or the application program itself.
ALLinBOX Hospitality
: This device of the ALLinBOX family does not have the shutter channel nor standard thermostat functionalities, therefore it will not be
possible to have the objects associated with these functionalities. These objects are those whose name begin with "[Cx]" in the case of blinds and shutter
actuators and "[Tx]" for the standard thermostat.
Number
Size
I/O
Flags
Data type (DPT)
Functional Range
Name
Function
1
1 Bit
C - - T -
DPT_Trigger
0/1
Reset 0
Voltage Recovery -> Sending of 0
2
1 Bit
C - - T -
DPT_Trigger
0/1
Reset 1
Voltage Recovery -> Sending of 1
3
1 Bit
I
C - W - -
DPT_Enable
0/1
Lock Manual Control
0 = Lock; 1 = Unlock
1 Bit
I
C - W - -
DPT_Enable
0/1
Lock Manual Control
0 = Unlock; 1 = Lock
4
1 Bit
C - - T -
DPT_Trigger
0/1
[Heartbeat] Object to Send '1'
Sending of '1' Periodically
5, 16, 27, 38
1 Byte
I
C - W - -
DPT_SceneControl
0-63; 128-191
[Ox] Scenes
0
–
63 (Execute 1
–
64); 128
–
191 (Save 1
–
64)
6, 17, 28, 39
1 Bit
I
C - W - -
DPT_BinaryValue
0/1
[Ox] On/Off
N.O. (0=Open Relay; 1=Close
Relay)
1 Bit
I
C - W - -
DPT_BinaryValue
0/1
[Ox] On/Off
N.C. (0=Close Relay; 1= Open
Relay)
7, 18, 29, 40
1 Bit
O
C R - T -
DPT_BinaryValue
0/1
[Ox] On/Off (Status)
0=Output Off; 1=Output On
8, 19, 30, 41
1 Bit
I
C - W - -
DPT_Enable
0/1
[Ox] Lock
0=Unlock; 1=Lock
9, 20, 31, 42
1 Bit
I
C - W - -
DPT_Start
0/1
[Ox] Timer
0=Switch Off; 1=Switch On
10, 21, 32, 43
1 Bit
I
C - W - -
DPT_Start
0/1
[Ox] Flashing
0=Stop; 1=Start
11, 22, 33, 44
1 Bit
I
C - W - -
DPT_Alarm
0/1
[Ox] Alarm
0=Normal; 1=Alarm
1 Bit
I
C - W - -
DPT_Alarm
0/1
[Ox] Alarm
0=Alarm; 1=Normal
12, 23, 34, 45
1 Bit
I
C - W - -
DPT_Ack
0/1
[Ox] Unfreeze Alarm
Alarm=0 + Unfreeze=1 => End
Alarm
13, 24, 35, 46
1 Bit
O
C R - T -
DPT_State
0/1
[Ox] Warning Time (Status)
0=Normal; 1=Warning
14, 25, 36, 47
4 Bytes
I/O
C R W T -
DPT_LongDeltaTimeSec
-2147483648 -
2147483647
[Ox] Operating Time (s)
Time in Seconds