ALLinBOX 1612 v2 / 88 / 46 / Hospitality
Technical Support:
39
1 Byte
O
C R - T -
DPT_Fan_Stage
0 - 255
[FCx] Fan: Speed Enumeration
(Status)
S0 = 0; S1 = 1
432
1 Byte
I
C - W - U
DPT_Scaling
0% - 100%
[FCx] Manual Fan: Percentage
Control
S0 = 0%; S1 = 0,4-33,3%; S2 =
33,7-66,7%; S3 = 67,1-100%
1 Byte
I
C - W - U
DPT_Scaling
0% - 100%
[FCx] Manual Fan: Percentage
Control
S0 = 0%; S1 = 1-50%; S2 = 51-
100%
1 Byte
I
C - W - U
DPT_Scaling
0% - 100%
[FCx] Manual Fan: Percentage
Control
S0 = 0%; S1 = 1-100%
433
1 Byte
O
C R - T -
DPT_Scaling
0% - 100%
[FCx] Fan: Speed Percentage
(Status)
S0 = 0%; S1 = 33,3%; S2 =
66,6%; S3 = 100%
1 Byte
O
C R - T -
DPT_Scaling
0% - 100%
[FCx] Fan: Speed Percentage
(Status)
S0 = 0%; S1 = 1-50%; S2 = 51-
100%
1 Byte
O
C R - T -
DPT_Scaling
0% - 100%
[FCx] Fan: Speed Percentage
(Status)
S0 = 0%; S1 = 1-100%
434
1 Byte
I
C - W - U
DPT_Scaling
0% - 100%
[FCx] Cooling Fan: Continuous
Control
0 - 100%
1 Byte
I
C - W - U
DPT_Scaling
0% - 100%
[FCx] Cooling Valve: PI Control
(Continuous)
0 - 100%
435
1 Byte
I
C - W - U
DPT_Scaling
0% - 100%
[FCx] Heating Fan: Continuous
Control
0 - 100%
1 Byte
I
C - W - U
DPT_Scaling
0% - 100%
[FCx] Heating Valve: PI Control
(Continuous)
0 - 100%
436
1 Bit
I
C - W - U
DPT_OpenClose
0/1
[FCx] Cooling Valve: Control
Variable (1 bit)
0 = Open Valve; 1 = Close Valve
1 Bit
I
C - W - U
DPT_Switch
0/1
[FCx] Cooling Valve: Control
Variable (1 bit)
0 = Close Valve; 1 = Open Valve
437
1 Bit
I
C - W - U
DPT_OpenClose
0/1
[FCx] Heating Valve: Control
Variable (1 bit)
0 = Open Valve; 1 = Close Valve
1 Bit
I
C - W - U
DPT_Switch
0/1
[FCx] Heating Valve: Control
Variable (1 bit)
0 = Close Valve; 1 = Open Valve
438
1 Bit
O
C R - T -
DPT_OpenClose
0/1
[FCx] Cooling Valve (Status)
0 = Open; 1 = Closed
1 Bit
O
C R - T -
DPT_Switch
0/1
[FCx] Cooling Valve (Status)
0 = Closed; 1 = Open
1 Bit
O
C R - T -
DPT_OpenClose
0/1
[FCx] Valve (Status)
0 = Open; 1 = Closed
1 Bit
O
C R - T -
DPT_Switch
0/1
[FCx] Valve (Status)
0 = Closed; 1 = Open
439
1 Bit
O
C R - T -
DPT_OpenClose
0/1
[FCx] Heating Valve (Status)
0 = Open; 1 = Closed
1 Bit
O
C R - T -
DPT_Switch
0/1
[FCx] Heating Valve (Status)
0 = Closed; 1 = Open
440
1 Bit
O
C R - T -
DPT_Switch
0/1
[FCx] Cooling Valve: Anti-Seize
Protection (Status)
0 = Not Active; 1 = Active
1 Bit
O
C R - T -
DPT_Switch
0/1
[FCx] Valve: Anti-Seize Protection
(Status)
0 = Not Active; 1 = Active