When two alarms are configured, ACTinBOX MAX6 could carry out different actions to two
external events.
Figure 3.14. Alarms
Configure the following parameters:
Number of alarms:
set whether to use one or two alarms. Both of them can be
independently managed through their corresponding communication objects (“[CX] Alarm”
for Alarm 1 and “[CX] Alarm 2” for the second one).
Alarm 1 is higher priority than Alarm 2. This means that if a channel is in Alarm 2 status
and Alarm 1 occurs the shutter will change to Alarm 1 status and it shall not come back to
Alarm 2 until Alarm 1 goes off. Whereas if the channel is in Alarm 1 status and Alarm 2
occurs, Alarm 1 prevails.
Trigger value:
set the value (“1” or “0”) to activate the alarm status. An alarm status
will be activated when the value set in this field is sent to the object “[CX] Alarm” (or “[CX]
Alarm2”).
Cyclical monitoring period (minutes):
parameterize the time on which the alarm
will be activated again (automatically) after the last No Alarm order (“[CX] Alarm" =
opposite value to trigger) received. When the cyclical monitoring period comes to its end,
ACTinBOX MAX6 activates the alarm, which will execute the parameterized action
(unless the output status has not changed). If a new alarm activation is not wanted, it will
be necessary to receive the opposite value to Trigger through the Alarm object before the
cyclical monitoring period ends.
The cyclical monitoring can be disabled by setting a 0 in this filed.