24

Symbol

Status

Action 

External voltage (only by M-Bus)

-

Flow 

existent

-

Attention! 

Check system /device 

for errors

 

 Symbol flashing: Data transmission

 

 Symbol constantly displayer: optical 

interface active

-

-

Emergency operation 

Exchange device

Complete symbol permanently displayed:

The meter is connected to LoRa server (join accept)

Wave symbol flashes, vertical bar permanently displayed:

Connection attempt with LoRa server (join request)

Only vertical bar permanently displayed:

Connection attempt with LoRa server failed (join failed)

Note: When the optical interface is activated, the wave symbol shows 

its status (see above)

Error codes show faults detected by zelsius® C5-IUF. If more than one error appears, the sum 

of the error codes is displayed: for example, error 1005 = error 1000 and error 5.

Code  Error type resp. possible reason 

Action

1

Temperature below of measuring range

Check sensors

2

Temperature above of measuring range

Check sensors

3

Short circuit return sensor

Check sensors

4

Interruption return sensor

Check sensors

5

Short circuit supply sensor

Check sensors

6

Interruption supply sensor

Check sensors

7

Battery voltage

Exchange device

8

Hardware error

Exchange device

9

Hardware error

Exchange device

10

Error in the measuring system

Exchange device (**)

20

No water in the measuring tube

Check operating pressure (**)

30

Reverse water flow detected

Check installation position (**)

40

Air inside the medium

Vent system (**)

50

Measured value outside overload range

Check dimensioning (**)

100

Hardware error

Exchange device

800

Wireless interface

Exchange device

1000

Status end of the battery

Exchange device respectively 

battery(*)

2000

Status initial verification expired

Exchange device

(*)

   The validity period for the calibration depends on the country, please observe  

the relevant national regulations. 

(**)  only by zelsius® C5-IUF

Status display / Error codes

The symbols in the table below show the meter’s operational status. The status 

messages only appear in the main display (energy). The temporary display of the 

warning triangle can be caused by special operating states and does not always 

mean that the device is malfunctioning. However, should the symbol be displayed 

over a longer period of time, you should contact the service company!

All manuals and user guides at all-guides.com

Содержание zelsius C5-ISF

Страница 1: ...and 3 inputs outputs qp 0 6 1 5 2 5 m h GB PDF Download Notice d installation Istruzioni per il montaggio Notice d installation et d utilisation 26 Compteur lectronique d nergie thermique et de frigor...

Страница 2: ...DFS 5 Einbau des Kugelhahns 5 Montage W rme K ltez hler 5 Montage Temperaturf hler 5 Einbau in Bestandstauchh lsen 6 Inbetriebnahme 6 Impulsein und ausg nge optional 7 M Bus optional 8 Programmierung...

Страница 3: ...idung von Kavitation bar 0 3 Nenndruck Spitzendruck PS PN 16 16 IP Schutzklasse 54 65 f r K ltez hlung und kombinier te W rme K ltez hlung Einbaulage horizontal horizontal um 90 gekippt vertikal Fall...

Страница 4: ...ind 0 2 m Pflegehinweise Kunststoffoberfl chen nur mit feuch tem Tuch reinigen Keine scheuern den oder aggressiven Reinigungsmit tel einsetzen Das Ger t ist ber die Einsatzdauer wartungsfrei Repa ratu...

Страница 5: ...igung kontrollieren Neuen Durchflusssensor flie rich tungs und lagerichtig einbauen Rechenwerk des W rmez hlers in die gew nschte Ableseposition drehen Montage Temperaturf hler Die Montage der Tempera...

Страница 6: ...nformer Temperaturf hler f r W rmez hler in Bestandstauchh lsen ver ffent licht in den PTB Mitteilungen 119 2009 Heft 4 eingesetzt werden Die Regelung hat nach aktuellem Stand den Geltungszeitraum bis...

Страница 7: ...erts Typische Beschaltung Der Anschlu eines externen Widerstandes kann notwendig sein um die Strombegrenzung zu gew hrleisten Inbetriebnahmeprotokoll gem PTB Richtlinie TR K9 ausf llen Hinweis Nur f r...

Страница 8: ...die ber eine integrierte Funkschnittstelle mit Antenne verf gen sind zur besseren Erkennbarkeit auf der Oberschale je nach Ausf hrung mit folgenden Symbolen gekennzeichnet wM Bus Beispiel Ausgang 1 E...

Страница 9: ...hfluss im Sendeintervall Daten wireless M Bus LoRaWAN Frequenzband 868 MHz 868 MHz Funkprotokoll wireless M Bus EN 13757 4 und gem Open Metering Standard OMS unterschiedliche Protokoll inhalte m glich...

Страница 10: ...ie vom letzten Stichtag bis heute Aktueller Monatsverbrauch W rmeenergie Aktueller Monatsverbrauch K lteenergie Aktuelles Monatsvolumen Maximaler Durchfluss Maximaler Monats Durchfluss Maximale Leistu...

Страница 11: ...sverh ltnisse durchlaufen E 20 E 25 E 30 E 35 E 40 E 45 E 50 P 20 P 25 P 30 P 35 P 40 P 45 P 50 E 0 E Ethylenglykol P Propylenglykol E 0 Wasser ohne Glykol Zusatz Bei Erreichen des gew nschten Wertes...

Страница 12: ...ung R cklauff hler Temperaturf hler pr fen 5 Kurzschluss Vorlauff hler Temperaturf hler pr fen 6 Unterbrechung Vorlauff hler Temperaturf hler pr fen 7 Batteriespannung Ger t austauschen 8 Hardwarefehl...

Страница 13: ...er mitnehmen und fachgerecht entsorgen Sofern dies bez glich keine andere vertragliche Regelung getroffen wurde k nnen alternativ die Altger te und Zubeh r auch bei unserer Betriebsst tte in D 09619 M...

Страница 14: ...the ball valve 17 Mounting heat cooling energy meter 17 Installation of the temperature sensors 17 Installation with existing immersion sleeves 18 Commissioning 18 Pulse inputs and outputs optional 19...

Страница 15: ...0 3 Nominal pressure peak pressure PS PN 16 16 IP protection class 54 65 for heating and cooling energy metering Installation position horizontal horizontal tipped through 90 vertical Heat carrier med...

Страница 16: ...ons Clean plastic surfaces with a damp cloth only Do not use any scouring or aggressive cleaning agents The device is maintenance free during the service life Repairs may only be carried out by the ma...

Страница 17: ...g position Installation of the temperature sensors The installation of the tempera ture sensors should be prefer ably symmetrical and as direct installation Do not remove the temperatur sensor if alre...

Страница 18: ...Installation with existing immersion sleeves In Germany the C5 can be put into use in connection with existing im mersion sleeves in accordance with the article Putting into use of MID homologated tem...

Страница 19: ...en sure an integrated current limiter Example Output 1 energy output Energy display XXXXX XXX Last position 0 001 MWh 1 kWh Output pulse 1 kWh U 3 30 V Imax 20 mA GND Pulse V Out white yellow green b...

Страница 20: ...Radio optional General information zelsius energy meters which have an integrated radio interface with an antenna are marked for better visibil ity on the upper cover with one of the following symbol...

Страница 21: ...l Data wireless M Bus LoRaWAN Frequency 868 MHz 868 MHz Radio protocol Wireless M Bus EN 13757 4 and according to the Open Metering Standard OMS different radio telegram contents are possible accordin...

Страница 22: ...g energy difference from last due date to now Heat energy difference from 1 of this month to now Cooling energy difference from 1 of this month to now Volume difference from 1 of this month to now Max...

Страница 23: ...hes With each short press on the button the following loop for different mixing ratios runs E 20 E 25 E 30 E 35 E 40 E 45 E 50 P 20 P 25 P 30 P 35 P 40 P 45 P 50 E 0 E ethylene glycol P propylene glyc...

Страница 24: ...uit supply sensor Check sensors 6 Interruption supply sensor Check sensors 7 Battery voltage Exchange device 8 Hardware error Exchange device 9 Hardware error Exchange device 10 Error in the measuring...

Страница 25: ...waste disposal via ZENNER is possible Your local or municipal authority or the local waste disposal company can give you information relating the collec tion points for your used equipment ZENNER will...

Страница 26: ...compteur d nergie thermique frigorifique 29 Connection des sondes de temp rature 29 Indications relatives au montage des doigts de gants existants 30 Mise en service 30 Entr es et sorties pour impulsi...

Страница 27: ...imale pour viter la cavitation bar 0 3 Pression nominale Pression maximale PS PN 16 16 Indice de protection 54 65 pour la mesure combin e de frigorie et d nergie thermique de frigorie Position d insta...

Страница 28: ...u r seau lectrique 230 V distance minimale 0 2 m Conseils d entretien Nettoyez les surfaces plastiques uniquement avec un chiffon humide N utilisez pas de d tergents abrasifs ou agressifs L appareil e...

Страница 29: ...eur de volume adaptateur Employez uniquement des mat riaux d tanch it neufs et sans d faut pas de chanvre ou simi laire Nettoyez les surfaces d tan ch it et assurez vous qu elles ne soient pas endomma...

Страница 30: ...vec type de sonde de temp rature TS 45 5 voir plaque signal tique sur le c ble les deux sondes doivent toujours tre mont es dans l agent caloporteur Le montage dans un doigt de gant n est pas autoris...

Страница 31: ...nt d une r sistance externe peut s av rer n cessaire pour garantir la limitation du courant U 3 30 V Imax 20 mA GND Pulse V Out blanc jaune vert marron impulsion Attendez pour la mise jour de l affich...

Страница 32: ...it s Les compteurs d nergie zelsius qui disposent d une interface radio int gr e avec l antenne sont marqu sur le capot sup rieur par le symbole suivant pour une meilleure visibilit wM Bus Exemple Sor...

Страница 33: ...nsmission Sp cifications wireless M Bus LoRaWAN Fr quence 868 MHz 868 MHz Protocole radio wireless M Bus EN 13757 4 et conforme Open Metering Stan dard OMS diff rents protocolles de donn es possibles...

Страница 34: ...re Energie la date rep re Energie frigorifique la date rep re Volume D bit Temp rature aller Temp rature retour Diff rence de temp rature Puissance instantan e Energie thermique Diff rence date date d...

Страница 35: ...ective les diff rentes proportions de m langes sont parcourues en boucle E 20 E 25 E 30 E 35 E 40 E 45 E 50 P 20 P 25 P 30 P 35 P 40 P 45 P 50 E 0 E Ethyl neglycol P Propyl neglycol E 0 Eau sans addit...

Страница 36: ...it sonde aller V rifier sondes de temp rature 6 Interruption sonde retour V rifier sondes de temp rature 7 Tension pile Remplacer l appareil 8 Erreur du mat riel Remplacer l appareil 9 Erreur du mat r...

Страница 37: ...votre appareil usag Les points de reprise de vos appareils usag s sont disponibles par exemple la mairie locale aupr s des d chetteries locales Zenner assure dans tous les cas une limination professi...

Страница 38: ...la a sfera 41 Installazione del contatore di calore raffrescamento 41 Installazione delle sonde di temperatura 41 Installazione con manicotti ad immersione esistenti 42 Messa in funzione 42 Ingressi u...

Страница 39: ...Pressione nominale pressione di picco PS PN 16 16 Classe di protezione IP 54 65 per la misurazione dell energia di riscaldamento e raffrescamento Posizione di installazione orizzontale orizzontale inc...

Страница 40: ...one durante gli anni di validit della taratura Le riparazioni possono essere eseguite solo dal produttore o da partner di assistenza autorizzati Manuale di installazione Indicazioni di sicurezza relat...

Страница 41: ...are la volumetrica nuova in base alla direzione di flusso e alla posizione Girare la parte elettronica del con tatore nella posizione di lettura desiderata Installazione delle sonde di tempe ratura L...

Страница 42: ...re installate direttamente nel fluido NON consentita l installa zione in pozzetti Installazione con manicotti ad im mersione esistenti Secondo l articolo Installazione della sonda MID per contatori di...

Страница 43: ...ne di corrente U 3 30 V Imax 20 mA GND Pulse V Out bianco giallo verde mar rone impulso Attendere l aggiornamento della temperatura sul display Al termine della messa in funzione apporre i sigilli con...

Страница 44: ...accia radio integrata con un antenna sono con trassegnati per una migliore visibilit sul coperchio superiore con uno dei seguenti simboli wM Bus Esempio Uscita 1 uscita energia elettrica Indicatore d...

Страница 45: ...tenza nell intervallo di trasmissione Dati wireless M Bus LoRaWAN Frequenza 868 MHz 868 MHz Protocollo radio wireless M Bus EN 13757 4 secondo Open Metering Stan dard OMS Possibili diversi protocolli...

Страница 46: ...di raffrescamento dall ultimo giorno fisso d azzeramento fino ad oggi Calore differenza dal 1 di questo mese ad oggi Raffrescamento differenza dal 1 di questo mese ad oggi Volume differenza dal 1 di q...

Страница 47: ...r il seguente elenco di numeri per diverse concentrazioni di miscele glicolate E 20 E 25 E 30 E 35 E 40 E 45 E 50 P 20 P 25 P 30 P 35 P 40 P 45 P 50 E 0 E glicole etilenico P glicole propilenico E 0 a...

Страница 48: ...torno Controllo delle sonde di temperatura 5 5 Controllo delle sonde di temperatura 6 Interruzione sonda della mandata Controllo delle sonde di temperatura 7 Voltaggio difforme della batteria Sostitui...

Страница 49: ...ata utile e che li smaltiscano in maniera corretta Per ulteriori informazioni potete contattare la ns sede al seguente numero telefonico 051 198 733 80 ZENNER assicurer sempre di informarvi sul corret...

Страница 50: ...Notice All manuals and user guides at all guides com...

Страница 51: ...All manuals and user guides at all guides com...

Страница 52: ...er bernehmen wir keine Haftung ZRI_SAP155769_191028 ZENNER International GmbH Co KG R merstadt 6 66121 Saarbr cken Germany Telefon 49 681 99 676 30 Telefax 49 681 99 676 3100 E Mail info zenner com In...

Отзывы: