21
IMPORTANT
Decommission Pyroack first
1.
Remove Mag fuse F3 from the rear of the Pyrorack (far left)
2.
Wait 5 seconds
3.
Remove the main fuse F4 (middle)
4.
Wait 5 seconds
5.
Remove the mains cable
6.
Remove the battery fuse F5. The unit shall be powered down at this
stage.
7.
Unplug environmental management cable
8.
Remove the Pyrorack from the server cabinet.
9.
Place on table upside down.
10.
Unscrew the 4 screws in the middle of the pyrorack.
11.
Pull discharged canister out and unscrew cable attachment.
12.
Replace with new canister.
13.
Follow commissioning steps.
7.7 Important tips.
Before working within the Zellabox ALWAYS ensure you follow these steps:
1.
Turn key switch to manual
2.
Isolate both zones 1 and 2 by pressing the isolate zones buttons located
on the front panel
3.
A beeping sound will continue intermittently as a reminder
4.
Once you have completed work within the MDC and you are ready to
close the doors press the isolate buttons 1 and 2 once more
5.
Turn the key switch back to the automatic position
6.
The Pyrorack should return to normal status
7.
Please note, if you isolate power to the Pyrorack and the fuses are still
inserted, the Pyrorack will still be active as it has 24 hour internal battery
backup.