background image


 
  

 
 
 
 

 

 
 
 
 
 

 

 

5.4

 

Copper

 

Piping

 

(see hand out in Zellabox)

1.

Cut the pipe ends with a pipe cutter

2.

Remove burrs with the cut surface facing downwards so 
that the chips do not enter the pipe

3.

Put the flare nuts on pipe

4.

Flare the pipe

5.

Check that the flaring is properly made

6

.    Never use old or pre-used pipes

 

 

 

Zellabox 

Safety

 

Instructions 

  

  

  

  

 

 

7.    Do not use mineral oil on flared part
8.

Incomplete flaring may cause gas leakage

9.

Use flare nut fixed to unit

10.

Use torque wrenches when tightening the flare nuts

11.

Protect ends from dust

12.

Use pipe bender

10.

NEVER use pipes thinner than 0.8mm even when it is 
available on the market.

Refrigerant Piping Work

1.

Flaring the pipe end.

1) Cut the pipe end with a pipe cutter.

2) Remove burrs with the cut surface facing 

downward so that the chips do not enter the pipe.

3) Put the flare nut on the pipe.

4) Flare the pipe.

5) Check that the flaring is properly made.

1) Do not use mineral oil on flared part.

2) Prevent mineral oil from getting into the system as this would reduce the unit life. 

3) Never use piping which has been used for previous installations. Only use parts which are provided with the unit.

4) Do never install a refrigerant drier to this unit.

5) The drying material may dissolve and damage the system.

6) Incomplete or improper flaring may cause refrigerant gas leakage.

WARNING

2.

Refrigerant piping.

1) Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.)

2) To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A.)

3) Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.

CAUTION

Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand.  Then tighten them fully with the torque wrenches.

2-1. Caution on piping handling

1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. 

Use a pipe bender for bending. 

2-2. Selection of copper and heat insulation materials

• When using commercial copper pipes and fittings, observe the following:
1) Insulation material:  Polyethylene foam

Heat transfer rate:  0.041 to 0.052 W/mK (0.024 to 0.030 Btu/fth˚F (0.035 to 0.045kcal/mh˚C))
Refrigerant gas pipe’s surface temperature reaches 230˚F (110˚C) max.
Choose heat insulation materials that will withstand this temperature.

2) Be sure to insulate both the gas and liquid piping and to provide 

insulation dimensions as below.

3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

Flare nut tightening torque

Gas side

Liquid side

1/2 inch

5/8 inch

1/4 inch

36.5- 44.5ft • Ibf

(49.5-60.3N • m)

45.6-55.6ft • Ibf

(61.8-75.4N • m)

10.4 -12.7ft • Ibf

(14.2-17.2N • m)

Gas side

Liquid side

15/18/24 class

O.D. 1/4 inch (6.4mm)

Gas pipe thermal insulation

Thickness 0.393 inch (8mm) Min.

Thickness 0.031 inch 

(0.8mm) (C1220T-O)

Thickness 0.039 inch 

(1.0mm) (C1220T-O)

Thickness 0.031 inch

(0.8mm) (C1220T-O)

1-9/16 inch (40mm) or more 1-15/16 inch (50mm)  or more 1-3/16 inch (30mm) or more

Minimum bend radius

24 class

O.D. 5/8 inch (15.9mm)

15/18 class

I.D. 0.551-0.630 inch

(14-16mm)

24 class

I.D. 0.630-0.709 inch

(16-20mm)

Liquid pipe thermal insulation

15/18 class

O.D. 1/2 inch (12.7mm)

15/18/24 class

I.D. 0.315-0.393 inch 

(8-10mm)

(Cut exactly at 

right angles.)

 Remove burrs

Check

Flare’s inner 
surface must 
be flaw-free.

The pipe end must 
be evenly flared in 
a perfect circle.

Make sure that the 
flare nut is fitted.

Set exactly at the position shown below.

A

Flaring

Die

A 0-0.020 inch (0-0.5mm)

Clutch-type

Flare tool for R410A

0.039-0.059 inch (1.0-1.5mm)

Clutch-type (Rigid-type)

0.059-0.079 inch (1.5-2.0mm)

Wing-nut type (Imperial-type)

Conventional flare tool

Do not apply refrigeration 
oil to the outer surface.

Flare nut

Apply refrigeration 
oil to the inner 
surface of the flare.

Do not apply refrigeration 
oil to the flare nut avoid 
tightening with over torque.

[Apply oil]

Torque wrench

Piping union

Flare nut

Spanner

[Tighten]

Wall

If no flare cap is 

available, cover the 

flare mouth with 

tape to keep dirt or 

water out.

Be sure to 

place a cap.

Rain

Gas pipe

Liquid pipe

Gas pipe 
insulation

Liquid pipe 
insulation

Finishing tape

Drain hose

Inter-unit wiring

Refrigerant Piping Work

1.

Flaring the pipe end.

1) Cut the pipe end with a pipe cutter.

2) Remove burrs with the cut surface facing 

downward so that the chips do not enter the pipe.

3) Put the flare nut on the pipe.

4) Flare the pipe.

5) Check that the flaring is properly made.

1) Do not use mineral oil on flared part.

2) Prevent mineral oil from getting into the system as this would reduce the unit life. 

3) Never use piping which has been used for previous installations. Only use parts which are provided with the unit.

4) Do never install a refrigerant drier to this unit.

5) The drying material may dissolve and damage the system.

6) Incomplete or improper flaring may cause refrigerant gas leakage.

WARNING

2.

Refrigerant piping.

1) Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.)

2) To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A.)

3) Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.

CAUTION

Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand.  Then tighten them fully with the torque wrenches.

2-1. Caution on piping handling

1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. 

Use a pipe bender for bending. 

2-2. Selection of copper and heat insulation materials

• When using commercial copper pipes and fittings, observe the following:
1) Insulation material:  Polyethylene foam

Heat transfer rate:  0.041 to 0.052 W/mK (0.024 to 0.030 Btu/fth˚F (0.035 to 0.045kcal/mh˚C))
Refrigerant gas pipe’s surface temperature reaches 230˚F (110˚C) max.
Choose heat insulation materials that will withstand this temperature.

2) Be sure to insulate both the gas and liquid piping and to provide 

insulation dimensions as below.

3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

Flare nut tightening torque

Gas side

Liquid side

1/2 inch

5/8 inch

1/4 inch

36.5-44.5ft • Ibf

(49.5-60.3N • m)

45.6-55.6ft • Ibf

(61.8-75.4N • m)

10.4 -12.7ft • Ibf

(14.2-17.2N • m)

Gas side

Liquid side

15/18/24 class

O.D. 1/4 inch (6.4mm)

Gas pipe thermal insulation

Thickness 0.393 inch (8mm) Min.

Thickness 0.031 inch 

(0.8mm) (C1220T-O)

Thickness 0.039 inch 

(1.0mm) (C1220T-O)

Thickness 0.031 inch

(0.8mm) (C1220T-O)

1-9/16 inch (40mm) or more 1-15/16 inch (50mm)  or more 1-3/16 inch (30mm) or more

Minimum bend radius

24 class

O.D. 5/8 inch (15.9mm)

15/18 class

I.D. 0.551-0.630 inch

(14-16mm)

24 class

I.D. 0.630-0.709 inch

(16-20mm)

Liquid pipe thermal insulation

15/18 class

O.D. 1/2 inch (12.7mm)

15/18/24 class

I.D. 0.315-0.393 inch 

(8-10mm)

(Cut exactly at 

right angles.)

 Remove burrs

Check

Flare’s inner 
surface must 
be flaw-free.

The pipe end must 
be evenly flared in 
a perfect circle.

Make sure that the 
flare nut is fitted.

Set exactly at the position shown below.

A

Flaring

Die

A 0-0.020 inch (0-0.5mm)

Clutch-type

Flare tool for R410A

0.039-0.059 inch (1.0-1.5mm)

Clutch-type (Rigid-type)

0.059-0.079 inch (1.5-2.0mm)

Wing-nut type (Imperial-type)

Conventional flare tool

Do not apply refrigeration 
oil to the outer surface.

Flare nut

Apply refrigeration 
oil to the inner 
surface of the flare.

Do not apply refrigeration 
oil to the flare nut avoid 
tightening with over torque.

[Apply oil]

Torque wrench

Piping union

Flare nut

Spanner

[Tighten]

Wall

If no flare cap is 

available, cover the 

flare mouth with 

tape to keep dirt or 

water out.

Be sure to 

place a cap.

Rain

Gas pipe

Liquid pipe

Gas pipe 
insulation

Liquid pipe 
insulation

Finishing tape

Drain hose

Inter-unit wiring

Please note: Pipe size is 9.5mm for cooling capacity 2kw up to 3.5kw (See enclosed 
manual with condenser) 

5 Single & Dual cooling

 

system

 

commissioning

 

steps:

12

Содержание Cubb

Страница 1: ...1 Zellabox Installation Manual...

Страница 2: ...mmissioning Reference for air conditioning contractor 5 1 Condenser 5 2 Commissioning 5 3 Wiring 5 4 Copper Piping 5 5 Start up Single Cooling 5 6 Start up Dual Cooling 6 Online Access PDView Access O...

Страница 3: ...ta storage equipment The facility in the form of a cabinet has a host of built in features which ensure that your server is secure accessible and fully portable The Micro Data Centre can accommodate y...

Страница 4: ...ote Caution needs to be taken when removing the side panels of the Micro Data Centre in particular when dealing with the 38U as they are heavy We recommend a 2 man lift when removing and re installing...

Страница 5: ...ED ELECTRICAL CONTRACTOR WITH THE NECESSARY TRAINING Zellabox Safety Instructions 3 1 Power Supply requirements Zellabox 3 2 Switchboard Operation Following the connection to mains power DEPENDING ON...

Страница 6: ...6 Zellabox Safety Instructions 3 Power connection 3 3 Power Supply diagram to PDU switchboard 12U Cubb only Cooling system RCD Mains power Cooling system UPS Power Non monitored sockets...

Страница 7: ...View FRONT VIEW ISOLATOR MAIN 3KVA UPS 6KVA UPS AVAILABLE POWER P ROT E CT I ON NO RCD DIVERTER SURGE 3 8 T O T AL C U T O U T 47 TOTAL CUT OUT 485 NOMINAL 19 INCH RACK CASE 10 1 8 1 8 1 8 1 8 RCD COO...

Страница 8: ...door is opened by the push button located inside the Zellabox See user manual for programming options Use card reader until you are ready for biometric access mode 4 3 L E D Key Pad Operation The defa...

Страница 9: ...issioning Once the Zellabox has been positioned in its proposed location and connected to power the air conditioning contractor can commission the cooling system Only once the air conditioning contact...

Страница 10: ...ble termination in condenser 4 core cable 1 Red Brown 2 Blue 3 White Green Earth 5 3 Wiring cont Electrical Hazard Ensure cooling system is in the OFF position on Zellabox base mounted switchboard and...

Страница 11: ...tem commissioning steps PLEASE NOTE WHEN PLUGGING THE CABLE CONNECTORS YOU SHOULD HEAR A CLICK TO CONFIRM CONTACT AFTER INSERTING THE PLUG ENSURE BOTH ORANGE AND GREY CABLES ARE LOCKED BY TURNING THE...

Страница 12: ...ape to keep dirt or water out Be sure to place a cap Rain Liquid pipe Inter unit wiring 2 Remove burrs with the cut surface facing downward so that the chips do not enter the pipe 3 Put the flare nut...

Страница 13: ...mode and FAN STRENGTH is on HIGH 9 Run both system together for 5 minutes ensure both systems are operating 10 Pull out both plugs without turning cooling system off from the permanent supply and plug...

Страница 14: ...ower case Z numeral 3 lower case L sign lower case B lower case O and lower case X c Accept the terms of use check box d Once connected to the PDU the following similar image should appear 4 Access th...

Страница 15: ...o OPTION 1 Press enter Use the following to access Login admin Password z3ll box Accept the terms of use check box OPTION 3 To access the Zellabox PDU through a network switch or something similar fol...

Страница 16: ...these steps Assign the desired IP address to the PDU by referring to OPTION 1 above Plug network cable switch directly into the PDU Access the PDU through local Display If you have any questions plea...

Страница 17: ...e next few slides Please note Accidental discharge will occur if this guide is not followed step by step For effective and safe installation follow the steps below Please note Accidental discharge wil...

Страница 18: ...nister to the Pyrorack by inserting the plug and tightening the washer 5 Reinsert the canister back into the Pyroack 6 Place the Pyrorack into position top of the Zellabox 7 3 Commissioning Steps 1 Fi...

Страница 19: ...1 and 2 by pressing the isolate zones buttons located on the front panel 3 A beeping sound will continue intermittently as a reminder 4 Once you have completed work within the MDC and you are ready t...

Страница 20: ...Warning Fire Suppression System Information 20...

Страница 21: ...issioning steps 7 7 Important tips Before working within the Zellabox ALWAYS ensure you follow these steps 1 Turn key switch to manual 2 Isolate both zones 1 and 2 by pressing the isolate zones button...

Страница 22: ...sted in the cooling system section as this will overheat the equipment The Zellabox Micro Data Centre is a PLUG N PLAY unit therefore once it has been installed by a qualified contractor the Micro Dat...

Страница 23: ...Zellabox Zellabox Pty Ltd PO Box 1035 Osborne Park DC Western Australia 6916 AUSTRALIA 1300 117 644 www zellabox com info zellabox com Version 2014 011 23...

Отзывы: