10. Slide the new belt inside around the heat exchanger
through the opening in the casing and the gasket.
11. Rotate the heat exchanger to get the belt properly in
place.
12. Replace the U-beam and reattach the shaft and the
U-beam screws.
13. Clean the new belt with the cleaning cloth to make
sure it is free of dirt and any grease.
14. Pull the belt onto the belt wheel.
15. Rotate the heat exchanger and ensure that the belt is
in its place and everything looks fine.
16. Vacuum clean the heat exchanger casing.
•
Rotate the heat exchanger when you are vacuuming
to be sure to clean everywhere.
17. Close the maintenance hatch.
18. Add some silicone lubricant onto the rubber strips
outside the heat exchanger casing.
19. Place the heat exchanger back into the unit.
20. Reconnect the bayonet connector to the socket.
21. Reconnect the power.
22. Make sure the heat exchanger rotates.