The ventilation unit contains moving parts (e.g. fans,
motor and belt of the rotating heat exchanger) that wear
out during use. Because of normal wear, these parts will
have to be changed during the ventilation unit´s lifetime.
The normal lifetime of wear parts is dependant of the
operating conditions and periods, which means that a
normal maintenance period cannot be defined for the
wear parts.
Maintenance notification
The control panel reminds you about regular
maintenance.
Filters
MAINTENANCE
The ventilation unit uses cartridge filters ISO ePM1 (F7) for
supply and ISOePM10 (M5) for extract.
The recommended maximum maintenance period for
cartridge filters is 6 months.
The unit does not need much maintenance. Sufficient
maintenance usually covers the following tasks:
•
changing filters
•
cleaning the heat exchanger (when sweeping the
ventilation ductwork)
•
cleaning the fans (when sweeping the ventilation
ductwork)
•
checking condensation water drain.
supply
filter ISO
ePM1(F7)
extract filter
ISO ePM10(M5)
Before starting maintenance, switch off the power
by removing the plug from the socket. Wait
approximately two (2) minutes before starting
maintenance. Although power has been shut
down, the fans will rotate and the electric heater
will be hot for a while.
DANGER
When some part of the unit is serviced, check also
if other parts are worn or needs to be cleaned.
For more information on maintenance actions, see
a video in the Help Center on our website at www.
enervent.com.
FOR INFORMATION
To acknowledge the maintenance remainder,
go to:
> Main menu > Settings > Alarm >
Acknowledge service reminder > ok
FOR INFORMATION