Troubleshooting
Table 13
PCB System Error Codes (Green LEDs)
Warning = FLASHING
Lock-out = STEADY
System
Error
Code
(COM
T Stat)
Fault
Description
Potential Causes
LD1
LD2
LD3
LD4
OFF
OFF
OFF
X
Er 1
High pressure
lockout
> 600 PSI
n
n
Low air flow (heating), low water flow (cooling)
n
n
Blower fan inoperable (heat mode)
n
n
Dirty air filter (heat mode)
n
n
Airflow bypassing air coil (heat mode)
n
n
Return air too hot (heat mode)
n
n
Air in risers (cool mode)
n
n
Dirty water strainer (cool mode)
n
n
Fouling of refrigerant-to-water heat exchanger (cool mode)
n
n
Faulty or mis-wired zone valve (cool mode)
n
n
Ball valves closed (cool mode)
n
n
Main water pump inoperable (cool mode)
n
n
Supply water too hot (cool mode)
n
n
Wiring harness connector not properly connected
OFF
OFF
X
OFF
Er 2
Low pressure
lockout
< 40 PSI
n
n
Low refrigerant charge
n
n
Blower fan inoperable (cool mode)
n
n
Airflow bypassing air coil (cool mode)
n
n
Ball valves closed (heat mode)
n
n
Main water pump inoperable (heat mode)
n
n
Faulty TXV
OFF
OFF
X
X
Er 4
Freeze
protection,
water side
n
n
Water temperature < 30°F or < 10°F (heating)
n
n
DIP switch 2 incorrectly set
n
n
Air trapped in risers (heat mode)
n
n
Ball valves closed (heat mode)
n
n
Faulty zone valve (heat mode)
n
n
Main water pump inoperable (heat mode)
n
n
Dirty water strainer (heat mode)
n
n
Refrigerant charge quantity below factory recommendation
OFF
X
OFF
OFF
Er 5
Freeze
protection,
air side, < 35°F
n
n
Blower fan inoperable (cooling)
n
n
Dirty air filter (cool mode)
n
n
Airflow bypassing air coil (cool mode)
n
n
Return air too cool (cool mode)
n
n
Oversized unit for application, not enough load
n
n
Refrigerant charge quantity above factory recommendation
OFF
X
OFF
X
Er 9,
Er 10
Condensate
overflow
n
n
Clogged drain line
n
n
Condensate switch has residual water contacting from unit
installation/removal
OFF
X
X
X
Er 11
Over/under
low voltage
protection
16VAC > voltage
> 30VAC
n
n
Loss of power, brown-out
n
n
Main power voltage not within acceptable range
X
OFF
OFF
OFF
Er 13
LWT sensor
failure
n
n
Sensor wiring not properly connected, broken wire
X
OFF
OFF
X
Er 14
DAT sensor
failure
n
n
Sensor wiring not properly connected, broken wire
X
OFF
X
OFF
Er 15
FP1 sensor
failure
n
n
Sensor wiring not properly connected, broken wire
n
n
Wiring harness connector not properly connected
X
OFF
X
X
Er 16
FP2 sensor
failure
n
n
Sensor wiring not properly connected, broken wire