Blower performance data
Table 9: Standard unit, PSC Motor
Unit Speed
Rated
airflow
Min
CFM
Airflow (CFM) at external static pressure (in. wg)
0
0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0.6 0.65 0.7 0.75 0.8 0.85 0.9 0.95
1
009
High
350
245
483 469 452 433 412 378 357 325 266
Low
368 354 334 311 288 267
012
High
450
315
653 635 612 588 560 532 468 435 408 334
Low
415 406 389 364 344 318
015
High
500
350
620 627 632 630 620 602 576 559 543 513 475 435 393
Low
369 382 388 386 388 383 377 368 355
018
High
620
434
856 839 815 795 769 739 692 645 611 591 563 510 455
Low
448 461 465 470 467 463 455 445
024
High
880
616
1103 1118 1121 1116 1109 1102 1083 1058 1022 960 867 769 700 658 619
Low
826 845 863 868 870 867 858 842 793 742 694 650 618
030
High
930
651
1263 1271 1266 1254 1233 1210 1191 1170 1135 1070 978 836 754 698 650
Low
929 952 967 969 968 965 949 933 898 833 756 702 654
036
High
1270
889
1338 1329 1324 1319 1316 1321 1323 1318 1298 1289 1280 1272 1243 1200 1168 1111 1001 848
Low
943 942 940 942 942 943 942 922 914 906 893
042
High
1380
966
1699 1695 1686 1674 1671 1659 1650 1642 1634 1615 1586 1569 1520 1489 1452 1395 1272 1206
Low
1159 1173 1172 1176 1180 1184 1185 1183 1182 1172 1159 1142 1120 1093 1057 1002
052
High
1700
1190
1842 1848 1855 1868 1878 1883 1880 1879 1883 1865 1846 1818 1809 1781 1752 1712 1670 1617 1520 1237
Low
1589 1636 1653 1663 1675 1683 1701 1700 1693 1688 1682 1665 1641 1620 1591 1563 1515 1442 1344
062
High
2120
1484
2071 2073 2076 2094 2093 2086 2079 2068 2051 26 1996 1957 1938 1906 1878 1839 1796 1742 1692 1579
Low
1589 1636 1653 1663 1675 1683 1701 1700 1693 1688 1682 1665 1641 1620 1591 1563 1515
072
High
2350
1645
2520 2500 2493 2479 2474 2448 2405 2384 2355 2289 2224 2176 2126 2078 2038 1996 1956 1895 1842 1772 1677
Low
1842 1848 1855 1868 1878 1883 1880 1879 1883 1865 1846 1818 1809 1781 1752 1712 1670
Notes:
n
n
Airflow in CFM with wet coil and clean air filter
n
n
All airflow is rated and shown above at the lower voltage if unit is dual voltage rated, e.g. 208V for 208-230V units.
n
n
Performance stated is at the rated power supply, performance may vary as the power supply varies from the rated.
Содержание HP Series