The vertical installation of the bottom cover of the outside wall panel requires the precise vertical
positioning of the bottom cover of the interior cover!
5.
Pull the unit out of the wall mounting pipe again. Drill a drill hole, and install the dowel from the installation
set or a different dowel suitable for the material.
When the square wall mounting pipe is installed, the plasterboard dowel must be screwed into the
EPP housing of the wall mounting pipe, and the bottom cover must be fastened using the
countersunk wood screw! The plasterboard dowel and countersunk wood screw are an integral
part of the installation set for the square wall mounting pipe.
6. Push the unit back in, and fix in place the bottom cover of the interior top cover to the drill hole using the screw from
the installation set or a screw suitable for the alternatively selected type of fastening.
Electrical
connections
Electrical connections are to be implemented in accordance with the existing standards specific to the
relevant country, and must only be performed by qualified personnel!
3.2.4.1
Connection for power supply
Prior to starting work, ensure that the mains supply line has no voltage!
On-site, a disconnection system has to be installed using a contact opening width in accordance with the
conditions from overvoltage category III for complete disconnection in the fixed electrical installation, in
accordance with the installation regulations.
The power supply is connected after the final positioning of the unit in the wall mounting pipe. In doing so, proceed as
follows:
1. Stripping the wires - Slip a WAGO luminaire terminal from the installation kit, together with the plug connection for
solid conductors, onto one wire of the mains supply line respectively.
2. Connect one wire of the unit connecting cable respectively to the clamping connection for the stranded wire of the
WAGO luminaire terminal for the L-conductor and the N-conductor. The WAGO luminaire terminal of the PE
conductor remains unassigned (ventilation unit corresponds with protection class
II
– protective insulation).