EN - 14
Menu P5
¨
Setting additional programmes
Additional programme values
submenu
description
Minimum
Maximum
General
reset
P50
Activation of the open fire programme.
0 (= No)
1 (= Yes)
0
P51
Confirming the presence of
a Preheater element
0 (= No)
1 (= Yes)
0
Only change if a preheater element is installed afterwards or a general reset is given.
P52
Setting the Preheater programme.
•
0; Guaranteed protection.
•
1; High protection.
•
2; Nominal protection.
•
3; Economy.
0
3
2
In
guaranteed
protection
mode
the Preheater element is switched on soonest; this level offers the best
guarantee of balanced ventilation. Vice versa, in
economy
mode
the Preheater element switches on at the
last possible moment; balanced ventilation is not guaranteed in this mode.
When commissioning the ComfoAir, the Preheater programme can usually be left at level 2:
nominal
mode
(factory setting). In areas with frequent cold spells in winter (frequent periods of -10°C or lower), level 1
should be selected:
high
protection
or even level 0:
guaranteed
protection
.
P53
Confirming an electrical connection with an extractor
hood.
0 (= No)
1 (= Yes)
0
If an extractor hood is electrically connected to the ventilation system, the user can set the extractor
hood ventilation levels via P29.
P54
Confirming the presence of a bypass.
0 (= No)
1 (= Yes)
1
The standard ComfoAir configuration includes a bypass. Therefore, leave the value at ‘1’.
P55
Confirming the presence of a Afterheater.
•
0; Afterheater not fitted
•
1; Afterheater fitted
•
2; Afterheater is fitted and is regulated by a Pulse
Width Modulation (PWM) signal.
0 (= No)
2 (= PWM)
0
P56
Setting the required air volume in the house.
• nL: ”normal air volume”.
• HL: "high air volume".
nL
HL
HL
Setting the air volume is the starting point for programming the air specifications and setting the fans.
P57
Setting the ComfoAir type.
• Li = ”Left-hand version”.
• Re = ”Right-hand version”.
Li
Re
Li
With delivery the ComfoAir is correctly pre-programmed at the factory.
After an general reset the pre-programming is lost and the setting must be reset.
The right setting is mentioned on the identification plate on top of the ComfoAir.
P58
Enter controller priorities.
• 0; The highest air setting is leading INCLUDING the
signals from the analogue inputs
• 1; The highest air setting is leading EXCLUDING the
signals from the analogue inputs
0
1
0