EN - 24
E1 /
E2
Supply fan / Exhaust
fan not rotating
Release the front panel
by unscrewing the screws.
Remove the plastic panel
in front of the control
circuit board
Is
there 230 VAC
power present
on the fan ?
Yes
No
Disconnect the power
from the ComfoAir.
Replace the control
circuit board.
Is a
control signal
(1,5 - 10 VDC)
present on
the fan?
Yes
No
Disconnect the
power from
the ComfoAir.
Replace the
control circuit
board
Replace the fan.
(See the maintenance
chapter of the fans)
Lift the front panel
from its hinges.
Disconnect the power
from the ComfoAir.
Activate the self-test
(P76 on 1)
Risk of electrocution.